Specifications

140
Transducers
AC Voltage Demand Transducers (Moderate Time Interval) [Insulated]
AC voltage demand transducers output DC current or DC voltage that is proportional to the
average value (demand value) of the AC voltage within a specified time interval.
Applications
Monitoring of voltage due to load fluctuation
For detecting abnormal voltages in devices such as small-scale generators
For preventing the detection of error due to flicker
T-51/T-101 Series
T-101HAV (DS)
T-101HAV (DS)
0.5
150V : 0.4
300V : 0.8
150V
300V
0.5kg
Standard
product
Immediate delivery
Quasi-standard
product
Within 20 days
Special
product
21 to 60 days
Symbol
Reference delivery period
Delivery period classification
Outer shape
Model name
Accuracy
(grade)
Input (AC)
Voltage Frequency
Box
50 and
60Hz
1mA :
5mA :
4~20mA :
100mV :
1V :
5V :
10V :
1~5V :
0~5kΩ
0~1kΩ
0~600Ω
5kΩ~
5kΩ~
5kΩ~
10k
Ω~
5k
Ω~
15s
30s
60s
120s
150s
180s
Specify
Output (DC)
Voltage or current and load
Time interval (to)
Ripple
1% P-P
or less
Consumption VA Auxiliary power supply
Delivery
period
classification
Weight
110VAC %
50 and 60Hz
Consumption VA: 5
+10
-15
Connection diagrams (Refer to p.156 for outer dimensions.)
VT
OUTPUT
Output
Auxiliary power supply
VMA MB±
Load
Note 1
Fig. 1 T-101HAV (DS)
150V
T-101HAV (DS)
30 seconds 5V 110VAC
Model name
Number of units
Time interval
Voltage or current
Output
Input
Voltage
Auxiliary power supply
2
Input/Output relationships
0
0
2.5
5
V
0
0.5
1
mA
75 150
0 150 300
V
0
0
3
5
V
0
14
12
20
mA
75 150
0 150 300
V
DC output
DC output
AC input AC input
Auxiliary
power
supply
Input
24V±10%
100, 105, 110, 115, 120V
%
200, 210, 220, 230, 240V
50~300V
0.1~20mA, 50mV~10V
DC
Output
AC
+10
-15
T-101HAV (DS)
Accuracy of time interval (to): ±20%
The accuracy of the time interval is the accuracy of the time at which
the output reaches a value corresponding to 95% of a fixed value
when input.
Error may occur when the waveform of the input voltage is distorted.
For example, when the third harmonic voltage is 15%, the error is approx. ±2.0%.
*1
*2
Manufacturable range
The time interval (to) refers to the time required for
an output (Io) to reach a value corresponding to 95%
of a fixed input value (I) when the input (I) is applied
continuously.
The output becomes substantially 100% at 3 times
the time interval (3to).
!
0.95!
to
(Time interval)
0
output
!o
Time t
Ordering method
Note 1. For low-voltage circuits, grounding of the secondary side of the instrument voltage transformer is unnecessary.