Specifications
139
Transducers
AC Current Demand Transducers (Moderate Time Interval) [Insulated]
AC current demand transducers output DC current or DC voltage that is proportional to the
average value (demand value) of the AC current within a specified time interval.
Applications
Protection of transmission lines
Checking transformer load state
T-101HAA (DS)
Outer shape
Box
Model name
T-101HAA(DS)
0.5 0.1
5A
1A
50 and
60Hz
0.5kg
110VAC %
50 and 60Hz
Consumption VA: 5
1% P-P
or less
Accuracy
(grade)
Consumption VA Auxiliary power supply
Delivery
period
classification
Weight
Input (AC) Output (DC)
Current Frequency
Voltage or current and load
Time interval (to)
Ripple
+10
-15
1mA :
5mA :
4~20mA :
100mV :
1V :
5V :
10V :
1~5V :
0~5kΩ
0~1kΩ
0~600Ω
5kΩ~∞
5kΩ~∞
5kΩ~∞
10k
Ω~∞
5k
Ω~∞
15s
30s
60s
120s
150s
180s
Specify
⎫
⎪
⎪
⎬
⎪
⎪
⎭
Standard
product
Immediate delivery
Quasi-standard
product
Within 20 days
Special
product
21 to 60 days
Symbol
Reference delivery period
Delivery period classification
Connection diagrams (Refer to p.156 for outer dimensions.)
OUTPUT
Output
Load
Auxiliary power supply
CT
AMA MB±
Note 1
Fig. 1 T-101HAA (DS)
5A
Model name
T-101HAA (DS)
Number of units
1
Time interval
Voltage or current
Output
Input
Current
180 seconds 4-20mA
Auxiliary power supply
110VAC
Input/Output relationships
0
0
2.5
5
V
0
0.5
1
mA
2.5 5
0 0.5 1
A
0
0
3
5
V
0
14
12
20
mA
2.5 5
0 0.5 1
A
DC output
DC output
AC input AC input
Auxiliary
power
supply
Input
24V±10%
100, 105, 110, 115, 120V
%
200, 210, 220, 230, 240V
0.1~5A
0.1~20mA, 50mV~10V
DC
Output
AC
+10
-15
T-101HAA (DS)
Accuracy of time interval (to): ±20%
The accuracy of the time interval is the accuracy of the time at which
the output reaches a value corresponding to 95% of a fixed value
when input.
Error may occur when the waveform of the input current is distorted.
For example, when the third harmonic content is 15%, the error is approx. ±2.0%.
*1
*2
Manufacturable range
The time interval (to) refers to the time required for
an output (Io) to reach a value corresponding to 95%
of a fixed input value (I) when the input (I) is applied
continuously.
The output becomes substantially 100% at 3 times
the time interval (3to).
!
0.95!
to
(Time interval)
0
output
!o
Time t
T-51/T-101 Series
Note 1. For low-voltage circuits, grounding of the secondary side of the current transformer is unnecessary.