Specifications

First-order Lag Transducers [Non-insulated]
These transducers apply a time constant to the DC input signal and delay the response
speed.
The time constant can be set to any value between 1 and 60 seconds.
Applications
Averaging highly fluctuating signals
Prevents control system oscillation
T-51/T-101 Series
Transducers
137
Outer shape
Box
Model name
Time constant Ripple
Voltage or current and load
Output (DC)
Auxiliary power supply
Weight
Delivery
period
classification
0.4kg
Accuracy
class
Input (DC) and input resistance
110VAC %
50 and 60Hz
Consumption VA: 3
+10
-15
0.5T-51DS 1% P-P or less
: 0~5kΩ
: 0~1kΩ
: 0~600Ω
: 5kΩ~
: 5kΩ~
: 5kΩ~
: 10kΩ~
: 5kΩ~
1mA
5mA
4~20mA
100mV
1V
5V
10V
1~5V
The input and output are not insulated.
The time constant can be set arbitrarily.
*1
*2
100mV
1V
5V
10V
1~5V
1mA
5mA
4~20mA
100k
Ω
or more
Input voltage
drop: 200mV
or less
1 to 60s
Accuracy: ±20%
with respect
to set value
Standard
product
Immediate delivery
Quasi-standard
product
Within 20 days
Special
product
21 to 60 days
Symbol
Reference delivery period
Delivery period classification
Auxiliary
power
supply
Input
24V±10%
100, 105, 110, 115, 120V
%
200, 210, 220, 230, 240V
60mV~10V, 0.5mA~0.1A
0.1~20mA, 50mV~10V
DC
Output
AC
+10
-15
T-51DS
Manufacturable range
Model name
T-51DS
Number of units
2
Auxiliary power supply
110VAC
Input
Voltage or current
4-20mA
Output
Voltage or current
0-5V
Time constant, time interval and response speed relationship
Usage example
100
%
50
0
0
Input
output
63%
95%
99%
τ 3τ
Time constant (63% output)
Time interval (95% output)
Response speed (99% output)
τ:
3τ:
4.6τ:
4.6τ
VT
CT
Active power
transducer
T-101HW
First-order lag
transducer
T-51DS
Instantaneous value
3-minute time interval
demand value
Time constant τ=60
second setting
Connection diagrams (Refer to p.156 for outer dimensions.)
Fig. 1 T-51DS
OUTPUT
INPUT
Output
Input
Auxiliary power
supply
Input and
output are not
insulated.
MA MB
Front view
12.5
Span adjuster
Power supply
indicator (lamp)
50
100
80
115
130
12.5
Zero adjuster
Time constant adjustment
17.5
12
6
R
3
8.8
Fig. 1 T-51DS
The time constant (τ) refers to the time required for an output value to
reach 63% of a fixed input value when the input is applied continuously.
For measurement of moderate time interval active power demand
T-51DS
Ordering method