Specifications
(Insulated/Non-insulated)
Transducers
134
Input/Output relationships
0
0
2.5
5
V
0
0.5
1
mA
50 100
0 100 200
C°
0
0
3
5
V
0
14
12
20
mA
50 100
0 100 200
C°
DC output
Input (temperature)
DC output
Input (temperature)
Inspection and adjustment
Perform the following procedure to check whether or not a transducer is operating normally.
qInstall an inspection resistor at (near) the installation location of the resistance bulb and connect the inspection resistor.
wCheck whether or not the transducer outputs a value corresponding to the inspection temperature. If there is an error in
output, adjust the transducer using the output adjuster.
A GR-2 standard resistor (sold separately) can be used as an inspection resistor (see p.149).
Connection diagrams (Refer to p.156 for outer dimensions.)
Fig. 1 T-51TP Fig. 2 T-101TPZ
OUTPUT
Output
Resistance bulb
Auxiliary power supply
A
M
A
BC(b)
MB
OUTPUT
Output
Resistance bulb
Auxiliary power supply
A
M
A
BC(b)
MB
Model name
T-101TPZ
Auxiliary power supply
110VAC
Number of units
10
Input
Temperature resistance bulb
0–200°C Pt100Ω
Output
Voltage or current
4–20mA
Ordering method