Specifications

128
Transducers
DC Reverse Transducers [Non-insulated]
DC reverse transducers input DC voltage (or current) and output DC voltage or DC current
inversely proportional to the input; for example, as the input signal increases from 0% to
100%, the output signal decreases from 100% to 0%.
Applications
Monitoring of deviation amount in combination with devices such as a position
detection sensor or temperature transducer
To create a fail-safe arrangement in the event of losing control power supply
T-51/T-101 Series
T-51DR
Outer shape
Box
Model
name
T-51DR 0.25
1% P-P or less
0.2s or less
0.4kg
Accuracy
(grade)
Input (DC) and input resistance
Auxiliary power
supply
Weight
Delivery period
classification
Output (DC)
Voltage or current and load
Ripple/Response speed
0~100mV
0~1V
0~5V
0~10V
1~5V
0~1mA
0~5mA
4~20mA
100kΩ or more
Input voltage drop
:
200mV or less
1~0mA : 0~10kΩ
5~0mA : 0~2kΩ
20~4mA : 0~600Ω
100~0mV : 500Ω~
1~0V : 500Ω~
5~0V : 500Ω~
10~0V : 1kΩ~
5~1V : 500Ω~
110VAC %
50 and 60Hz
Consumption
VA: 3
+10
-15
Standard
product
Immediate delivery
Quasi-standard
product
Within 20 days
Special
product
21 to 60 days
Symbol
Reference delivery period
Delivery period classification
Resistance between input terminals
The input and output are not isolated.
Please inquire separately regarding input specifications exceeding 300V.
*1
*2
*3
Input
Input resistance
60mV~50V
100kΩ
over 50V~300V
2kΩ
/V
0.5mA~0.1A
Input voltage drop: 200mV or less
Input 60mV~300V, 0.5mA~0.1A
0.1~20mA, 50mV~10V
100, 105, 110, 115, 120V
%
200, 210, 220, 230, 240V
24V±10%
T-51DR
Output
*3
Auxiliary
power
supply
DC
AC
+10
-15
Manufacturable range
Model name
T-51DR
Number of units
3
Auxiliary power supply
110VAC
Output
Voltage or current
20-4mA
Input
Voltage or current
0-5V
Input/Output relationships
0
0
2.5
5
V
0
0.5
1
mA
2.5 5V
00.51V
0
0
3
5
V
0
14
12
20
mA
2.5 5V
00.51V
DC output
DC input
DC output
DC input
Usage examples
100%
Water level sensor
4~20mA
Usage amount
DC reverse transducer
T-51DR
20~4mA
0%
0%
Furnace
Target value = 100°C
Present value = 20°C
Deviation value = 80°C
0~100°C
4~20mA
100°C
80°C
0°C
20~4mA
Temperature deviation
value
Temperature transducer
T-51TP
T-101TC
DC reverse transducer
T-51DR
Temperature
sensor
Heater
Connection diagrams (Refer to p.156 for outer dimensions.)
Fig. 1 T-51DR
OUTPUT
INPUT
Output
Auxiliary power supply
Input and output
are not insulated.
Input
MA MB
For usage amount measurement
For measurement of deviation amount from target value
Ordering method