Specifications

[Insulated]
Transducers
120
“Inherent reactive power” of reactive power transducers
Input/Output relationships
0
0
2.5
5
V
0
0.5
1
mA
500 1000var
0
0
3
5
V
0
14
12
20
mA
500 1000var
1000
-5
0
5
V
-1
0
1
mA
0 1000var
LEAD LAG
LEAD LAG
1000
0
3
5
V
0
14
12
20
mA
0 1000var
DC output
AC input
DC output
AC input
DC output
AC input
DC output
AC input
Connection diagrams (Refer to p.156 for outer dimensions.)
Please specify in the case of S Series.In the case of 3-phase, 4-wire,
please specify the phase
voltage and line voltage.
Although manufacturing will be performed even when specified in kvar units,
the specifications will be converted to var units on the rating nameplate.
Model name
T-101HVAR
Frequency
60Hz
Number of units
3
Auxiliary power supply
110VAC
Phase-wire
Input
Voltage Current
3P3W 110V 5A
Output
Voltage or current
–5–0–5V
Transducer inherent
reactive power value
LEAD1000–0–LAG1000var
Load
VT
CT
OUTPUT
Output
Auxiliary power
supply
P2P1 C1P3
3
2
1
CT
C2
MA MB
C3C1 C2 C3
Load
VT
CT
OUTPUT
Output
Auxiliary power
supply
MA MB
P2P1 C1P3
3
2
0
1
C3
CT
CT
C2C1 C3C2
Note 1 Note 1
Fig. 2 T-101HVAR 3P4W
T-101SVAR 3P4W
Fig. 1 T-101HVAR 3P3W
T-101SVAR 3P3W
Inherent reactive power value calculation example
* The primary-side reactive power (kvar) mentioned here is not the full-load reactive power based on the VT-CT rating. It refers to the reactive power value kvar
(primary-side reactive power value equivalent to the rated output value) to be controlled according to the power factor.
A reactive power transducer can be manufactured if the transducer inherent reactive power
is within the range of the table on the left.
In the case of bidirectional input, calculate using the larger of the lag or lead reactive powers.
In the case of a 3-phase, 3-wire, VT 6600/110V, CT 200/5A arrangement with the primary-side reactive power being 1200kvar:
Transducer inherent reactive power Q
0
= = = 0.500 (kvar)
primary-side reactive power (kvar)
VT ratio CT ratio
1200kvar
6600/110 200/5
*3.
*4.
*5.
Note 1.
In the case of unidirectional input, the lag side (LAG) is the reactive power unless particularly specified.
A CT must be inserted and used in the current circuit because reactive power transducers are three-current systems.
Operation will be abnormal when the input of the three-phase circuit is a negative-phase sequence.
For low-voltage circuits, grounding of the secondary sides of the instrument voltage transformer and current transformer is unnecessary.
Ordering method
Q
0
=
primary-side reactive power (kvar)
VT ratio CT ratio