Specifications
114
Transducers
T-51HSS
T-51/T-101 Series
Current Transducers (Saturated Power) [Insulated]
Suited for motor circuits, heater circuits and other circuits in which an overcurrent flows during
startup.
When combined with a needle indicator, an indicator with the scale expanded three-fold is realized.
110VAC %
50 and 60Hz
Consumption VA: 3
Outer shape
Box
Model
name
Accuracy
(grade)
Consumption
VA
Auxiliary power
supply
Weight
Delivery
period
classification
Ripple/
Response
speed
Input (AC) Output (DC)
Current Frequency Voltage or current and load
T-51KSS (*1)
0~0.8~(1)mA : specify 5kΩ
or less
0~4~(5)V : specify 50kΩ
or less
The load resistance connected to T-51KSS is fixed. In the case of current output, please specify a
resistance value no more than that shown in the table above; specify a resistance value no less than that
shown in the table above in the case of voltage output.
Models with 2- to 5-times expanded saturated power can also be manufactured.
Error may occur when the input waveform is distorted.
For example, when the third harmonic content is 15%, the error is approx. ±5% for T-51KSS and ±2% for
T-51HSS.
The tolerance of the maximum saturated power is within ±10% (% in respect to saturated power value).
*1
*2
*3
*4
Standard
product
Immediate delivery
Quasi-standard
product
Within 20 days
Special
product
21 to 60 days
Symbol
Reference delivery period
Delivery period classification
+10
-15
5% P-P
or less
1s
or less
1% P-P
or less
1s
or less
—
T-51KSS
T-51HSS
0.5
0.5
0.4
0.1
0.4kg
0.4kg
T-51HSS
0~0.8~(1)mA : 0~5kΩ
4~16~(20)mA : 0~600Ω
0
~
4
~
(5)V : 5k
Ω
~∞
0~8~(10)V : 10k
Ω
~∞
0~5~15A
0~1~3A
50 and 60Hz
0~5~15A
0~1~3A
50 and 60Hz
Manufacturable range
Connection diagrams
(Refer to p.156 for outer dimensions.)
Input/Output relationships
Auxiliary
power
supply
Input
T-51KSS
0.1~7.5A
Only specifications in the table above
—
— 24V, 100~120V
0.1~5A
0.1~20mA 50mV~10V
100, 105, 110, 115, 120V
%
200, 210, 220, 230, 240V
T-51HSS
DC
Output
AC
The voltage tolerance of a 24VDC auxiliary power supply is ±10%.
The voltage tolerance of a 100~120VDC auxiliary power supply is %.
+10
-15
+15
-25
Specify three values for the output.
Model name
T-51KSS
Load resistance
3kΩ
Number of units
10
Input
Current
0-5-15A
Output
Voltage or current
0-0.8-1mA
Model name
T-51HSS
Number of units
20
Auxiliary power supply
110VAC
Input
Current
0-5-15A
Output
Voltage or current
4-16-20mA
K Series
H Series
0
0
2
(5)
V
0
0.4
40.8
(1)
mA
0.5 3
02.5 15
1
5
A
0
0
10
4
(20)
mA
16
0.5 3
02.5 15
1
5
A
DC output
AC input
DC output
AC input
Fig. 1 T-51KSS
OUTPUT
Output
Load
A ±
Fig. 2 T-51HSS
OUTPUT
Output
Load
Auxiliary power supply
CT
A ±
MA MB
Note 1 Note 1
Note 1. For low-voltage circuits, grounding of the secondary side of the current transformer is unnecessary.
Ordering method