7.7.2 Device specification ranges
The following is the device and device number range that can be used in the access of device
memory.
Each device is composed of five characters.
Device (1 character, 2 characters with timer and counter) + device number (4 characters, 2
characters with timer and counter) = 5 characters.
1 ) Bit devices
In FX series, the timer coil (TC) and counter coil (CC) are not supported.
2 ) Word devices
* Only CN000 to CN199 can be used.
(C200 to C255 of 32 bit counter or high speed counter cannot be used.)
Device
Device specification characters
Decimal/octal
expression
Usable
command
FX
0N
FX
1S
FX, FX
2C
FX
1N
FX
2N
,
FX
2NC
BR,
BW,
BT
WR,
WW,
WT
Inputs (X)
X0000
X0177
X0000
X0017
X0000
X0337
X0000
X0177
X0000
X0267
Octal
'
'
Outputs (Y)
Y0000
Y0177
Y0000
Y0015
Y0000
Y0337
Y0000
Y0177
Y0000
Y0267
Auxiliary relays (M)
M0000
M0511 M0000
M1535
M0000
M3071
Decimal
States (S)
S0000
S0127 S0000
S0999
Special auxiliary relays (M)
M8000
M8254 M8000
M8255
Timer contacts (T)
TS000
TS063 TS000
TS255
×
Counter contacts (C)
CS000
CS031
CS235
CS254
CS000
CS255
Device
Device specification characters
Decimal/
octal
expression
Usable
command
FX
0N
FX
1S
FX, FX
2C
FX
1N
, FX
2N
,
FX
2NC
BR,
BW,
BT
WR,
WW
WT
Timer current value (T)
TN000
TN063 TN000
TN255
Decimal
×
'
'
Counter current value(C)
CN000
CN031
CN235
CN254
CN000
CN255
'
*
Data registers (D)
D0000
D0255 D0000
D0999 D0000
D7999
'
File registers (D)
D1000
D2499
D1000
D2999
RAM file registers (D)
D6000
D7999
Special data registers(D)
D8000
D8255 D8000
D8255
Notes
1 ) When using bit devices specified in word units (WR, WW, WT), the number of the
head device must be a multiple of 8 (or if an octal device end in 0) e.g. X30, M24.
2 ) The special auxiliary relays (M8000 to M8255) and special data registers (D8000
to D8255) can be read only, write only, and received for system use.
If an attempt is made to write outside the write enable range, an error may occur in
the programmable controller. Accordingly, for details of special auxiliary relays and
special data registers, see the programmable controller manual.