User`s manual

FX communication
Computer link 7
7-11
7
7.4.4 Time-out Check Time
The time out check time refers to the duration after termination of receive (final character
received) of a failed transmission from the computer to the programmable controller, until the
send sequence is initialized.
This check time is specified as follows depending on the model and version of the programmable
controller.
To set the time-out check time as 60 ms:
It must be noted that the time-out check time is not updated until the next character is received,
and hence must be set to at least more than the time necessary to receive one character at the
baud rate (transmission speed) in use. When 1 character = 12 bits, the minimum setting of time-
out check time is as follows.
PC series Setting range
FX
0N
, FX
1S
, FX
1N
1 to 255 (10 to 2,550 ms) ; however, a setting of “0” gives 100 ms.
FX, FX
2C
, FX
2N
, FX
2NC
1 to 3,276 (10 to 32,760 ms) ; however, setting of “0” gives 100 ms.
Baud rate (bps) Time to receive one character (ms) Time-out check time (set value)
300 40 50ms (5)
600 20 30ms (3)
1200 10 20ms (2)
2400 5 10ms (1)
4800 2.5 10ms (1)
9600 1.25 10ms (1)
19200 0.625 10ms (1)
M8002
FNC 12
MOV
K6
D8129
Other function information:
In the case of FX
0N