User`s manual

FX communication
Introduction 1
1-4
2 ) FX
1N
(Shielded twisted-pair cable)
*2 When including an FX
1N
-485-BD in the system configuration, thais, total extension distance
has a max of 50m
(164' 0")
.
3 ) FX
1S
(Shielded twisted-pair cable)
*3 When including an FX
1N
-485-BD in the system configuration, thais, total extension distance
has a max of 50m
(164' 0")
.
4 ) FX
0N
(Shielded twisted-pair cable)
5 ) FX, FX
2C
(Shielded twisted-pair cable and glassfiber cable)
Note;
Parallel link is only possible between the same series of PLC’s, or between other
series in the same group. However, parallel link between each group cannot be
achieved.
Groups are separated as follows.
#
##
#
,
$
$$
$
Using interface Extension distance
FX
1N
FX
1N
-485-BD Max. 50m (164' 0")
FX
1N
-CNV-BD + FX
0N
-485ADP
Max. 500m (1640' 5")
*2
FX
1N
-CNV-BD + FX
2NC
-485ADP
#
##
#
,
$
$$
$
Using interface Extension distance
FX
1S
FX
1N
-485-BD Max. 50m (164' 0")
FX
1N
-CNV-BD + FX
0N
-485ADP
Max. 500m (1640' 5")
*3
FX
1N
-CNV-BD + FX
2NC
-485ADP
#
##
#
,
$
$$
$
Using interface Extension distance
FX
0N
FX
0N
-485ADP
Max. 500m (1640' 5")
FX
2NC
-485ADP
#
##
#
,
$
$$
$
Using interface Extension distance
FX
2
, FX
2C
FX
2
-40AW (Shielded twisted-pair cable) Max. 10m (32' 9")
FX
2
-40AP (Glassfiber cable) Max. 50m (164' 0")
Group No. Series
Group 1 FX
2N
, FX
2NC
Group 2 FX
1N
Group 3 FX
1S
Group 4 FX
0N
Group 5 FX, FX
2C