User`s manual
12
FX communication
Diagnostics 12
12-7
12.6 FX
2N
-232IF
12.6.1 Error code
When an error occurs while data is sent or received, BFM #28 b3 is set to ON and the error code
is saved in BFM #29.
12.6.2 Diagnostics
1 ) Check the status of the POWER LED provided in the FX
2N
-232IF.
• When it is Lit, the power source is correctly supplied.
• If it is extinguished, supply from the power source correctly.
2 ) Check the status of the SD LED and the RD LED provided in the FX
2N
-232IF.
• If the RD LED is not Lit while data is received or the SD LED is not Lit while data is sent,
check the installation and the wiring.
• When the RD LED is Lit while data is received or the SD LED is Lit while data is sent, the
installation and the wiring are correct.
3 ) Make sure that the communication setting (BFM #0) of the FX
2N
-232IF is equivalent to that of
the external equipment. If they are not equivalent each other, make them equivalent.
4 ) Make sure the timing of data send/receive. For example, make sure that the counterpart
equipment is ready for receive before starting to send data to it.
5 ) When the terminator is not used, check whether the send data capacity is equivalent to the
acceptable data capacity. If the send data capacity may be changed, use the terminator.
6 ) Make sure that the external equipment is correctly operating.
7 ) Check whether the type of send data and the type of receive data are equivalent. If they are
different, make them equivalent.
Code Description Causes and countermeasures
0 No error
1
Receive parity error, overrun error, framing
error
Communication format such as baud rate is not
matched.
Control timing is not matched.
2 Undefined
3 Defective receive character Receive data is not ASCII code.
4 Receive sum check error
Receive sum is not equal calculated sum result
(BFM #16).
5
Receive buffer overflow (only in interlink
connection mode)
Receive byte count exceeds 512+30 bytes.
Decrease receive upper byte count (BFM #2),
and increase spare receive buffer area.
6 Baud rate setting error Non-existing baud rate is specified.
7 Receive CR error CR is not placed in correct position.
8 Receive LF error LF is not placed in correct position.
9 Send/receive initial terminator setting error Initial terminator is other than 01H to 1FH.
10 Receive terminator error
Receive terminator is not placed in correct
position or not matched.
11 Undefined
12 Transmission sequence error Transmission sequence is not matched.