Operating Conditions and Format Set Content
The programmable controller can change from using no protocol communication to programming
protocol (and back) by manipulating the RS instruction and Register D8120 and shown below.
1 ) With the RS instruction ON, move the data options shown below into the Register D8120 to
use no protocol communication.
2 ) To use programming protocol, turn the RS instruction OFF and move the data H0000 into the
communication format Register D8120. When the programmable controller is taken out of
RUN mode (by FX-PCS/WIN-E Software or the front panel switch), complete editing and
program downloads can be accomplished. On line changes can be performed with the
programmable controller in Run Mode.
Example of changing the communication format (D8120) between H0086 and H0000. The
programmable controller is first set for no protocol communication using the RS instruction.
Table: Set communication format (D8120)
Item
Content
H0086 H0186 H0286 H0386
Data length 7 Bit
Parity bit Even number (EVEN)
Stop bit 1 Bit
Baud rate (bps) 9600 bps
Header Off On Off On
Te r m in a to r Of f O n
X0
FNC 12
MOV
FNC 80
RS
X0
P
D0 K1 D1 K1
H0086 D8120
FNC 12
MOV
P
H0000 D8120