7.16 Report Slave ID (Command Code: 0x11)
Acquires the information of the slave (FX-Series MODBUS Communication ADP) mounted station into the
master.
1) Request message format (Master → Slave)
2) Response message format (Slave → Master)
(When completed normally)
The slave (FX-Series MODBUS Communication ADP) will return 'F3' as the PLC CPU type data to the
Master:
(When completed with an error)
*1. Exception and error codes are stored in special data registers and special auxiliary relays in the case
of error completion. Refer to Chapter 6 for storage location, confirmation methods, and other detailed
contents.
Function code
Function
code
(11
H)
Data
Function code
Function
code
(11
H)
Number of
bytes
(02
H)
PLC CPU
PLC CPU
STOP/RUN
state
(F3H)
type
00
H: STOP
FF
H: RUN
Data
Function code
Function
code
(91
H)
Exception
code*
1