User`s manual

61
FX3U Series Programmable Controllers
User’s Manual - MODBUS Serial Communication Edition
7 MODBUS Standard Commands
7.11 Diagnostics (Command Code: 0x08)
1
Outline
2
Specifications
3
System
Configuration
4
Wiring
5
Communication
Setup
6
Related
Devices and
Comm. Status
7
MODBUS
Standard
Commands
8
Master
Specification
9
Slave
Specification
10
Creating
Programs
7.11.5 Force listen only mode (sub-command code: 0x04)
Places a slave into the offline mode.
Used when disconnecting a slave from the network.
When FX-Series MODBUS Communication ADP is set in the listen only mode, the status is as follows:
Ignores all request messages except for those of restart communications option (Refer to Subsection
7.11.2).
Stops counting of the diagnostic counter (Refer to Chapter 6).
Continues recording with the communications event log (Refer to Section 9.5).
1) Request message format (Master Slave)
2) Response message format (Slave Master)
(When completed normally)
No response message is returned because the listen only mode (offline status) is active.
(When completed with an error)
*1. Exception and error codes are stored in special data registers and special auxiliary relays in the case
of error completion. Refer to Chapter 6 for storage location, confirmation methods, and other detailed
contents.
Note
1) Whether the FX-Series MODBUS Communication ADP has been switched to listen only mode or not is
indicated by M8404/M8424.
2) The listen only mode can be changed to online mode by either of the following:
- Restart communications option (Refer to Subsection 7.11.2)
- Power OFF ON
(L)
Data
(L)
Function code
Function
code
(08
H)
Sub-function code
Sub-function code
(0004
H)
(0000
H)
(H)
(H)
Data
Function code
Function
code
(88
H)
Exception
code*
1