7 MODBUS Standard Commands
7.11 Diagnostics (Command Code: 0x08)
1
Outline
2
Specifications
3
System
Configuration
4
Wiring
5
Communication
Setup
6
Related
Devices and
Comm. Status
7
MODBUS
Standard
Commands
8
Master
Specification
9
Slave
Specification
10
Creating
Programs
7.11 Diagnostics (Command Code: 0x08)
Executes the various diagnostics and checks the FX-Series MODBUS Communication ADP.
7.11.1 Return query data (sub-comand code: 0x00)
Returns the contents of the request message without change.
Used to check if the network or the target device is operating normally. (Loopback test)
1) Request message format (Master Slave)
2) Response message format (Slave Master)
(When completed normally)
The slave returns the request message received from the master without change.
(When completed with an error)
*1. Exception and error codes are stored in special data registers and special auxiliary relays in the case
of error completion. Refer to Chapter 6 for storage location, confirmation methods, and other detailed
contents.
(L)
Data
Function code
Function
code
(08
H)
Sub-function code
Sub-function code
(0000
H)
Arbitrary data
(H)
Data
Function code
Function
code
(88
H)
Exception
code*
1