7 MODBUS Standard Commands
7.8 Write Single Coil (Command Code: 0x05)
7.8 Write Single Coil (Command Code: 0x05)
Writes a value (ON/OFF) to one coil.
1) Request message format (Master → Slave)
2) Response message format (Slave → Master)
(When completed normally)
The slave returns the request message received from the master without change.
(When completed with an error)
*1. Exception and error codes are stored in special data registers and special auxiliary relays in the case
of error completion. Refer to Chapter 6 for storage location, confirmation methods, and other detailed
contents.
Data
(L) (L)
Function code
Function
code
(05
H)
Coil number
(0000
H to FFFFH)
ON/OFF specification
0000H : OFF
FF00
H : ON
(H)
(H)
Data
Function code
Function
code
(85
H)
Exception
code*
1