User`s manual
48
FX3U Series Programmable Controllers
User’s Manual - MODBUS Serial Communication Edition
7 MODBUS Standard Commands
7.3 Protocol Data Unit Formats by Commands
7.3 Protocol Data Unit Formats by Commands
This section describes MODBUS protocol data unit formats used by the FX-Series MODBUS Communication
ADP.
1) Precautions:
a) When the FX-Series MODBUS Communication ADP receives a broadcast request message:
Although the processing requested by the request message is performed etc., no response message
is sent to the master.
b) When the FX-Series MODBUS Communication ADP receives a request message in the listen only
mode:
Received messages are evaluated, but no action takes place and no response is sent. The only
exception is the "reset communication option" command (diagnosis 0x08 sub command 0x01). If this
command is received the slave recovers from listen only mode without sending a response, all
subsequent commands to this slave will be answered with a response as usual. For further
information refer to Chapter 6.
2) When the processing is completed in error at the slave (FX-Series MODBUS Communication ADP):
When the processing (read/write, diagnostics, etc.) requested by the request message is completed in
error, an exception code is sent to the master.
"Response message formats (when completed with an error)" in Section 7.4 to 7.18.
a) Storage location of exception code and error code. Refer to Chapter 6 for storage location,
confirmation methods, and other detailed contents.