Specifications

-
5
-
Item
Model
SRK71CF-BP SRC71CF-BP
Cooling capacity kW 7.03
Cooling power input kW 2.12
Energy efficiency ratio Btu/hW 11.33
Rating current A 10.6
Cooling capacity kW 6.3
Cooling power input kW 2.48
Energy efficiency ratio Btu/hW 8.67
Rating current A 12.4
Power source 1 Phase, 220V, 60Hz
Noise level Cooling Sound level dB Hi 45, Me 42, Lo 39 55
Exterior dimensions
Height × Width × Depth
mm
318 × 1098 × 248 750 × 880 × 340
Color Yellowish white Stucco white
Net weight kg 15 67
Refrigerant equipment
Compressor type & Q’ty
2JS318H5AB02(Rotary type) × 1
Motor kW 1.5
Starting method Line starting
Heat exchanger Slit fins & inner grooved tubing Straight fin & inner grooved tubing
Refrigerant control Capillary tubes + Electric expansion valve
Refrigerant
(3)
kg R22 1.75 (Pre-charged up to the piping length of 7m)
Refrigerant oil R 0.7 (ATMOS NM56M or SUNISO 4GDID)
Deice control Microcomputer control
Air handling equipment
Fan type & Q’ty
Tangential fan × 1 Propeller fan × 1
Motor W 46 73
Air flow (at High) (Cooling) CMM 20.5 60
Air filter, Q’ty
Polypropylene net (washable)
×
2
Shock & vibration absorber Cushion rubber (for compressor)
Electric heater ––
Operation control
Operation switch
Wireless-Remote control
Room temperature control Microcomputer thermostat
Pilot lamp RUN (Green), TIMER (Yellow), HI POWER (Green), ECONO (Orange)
Safety equipment
O.D mm (in) Liquid line: φ6.35 (1/4) Gas line: φ15.88 (5/8)
Connecting method Flare connecting
Attached length of piping Liquid line: 0.70m
Gas line : 0.63m
Insulation Necessary (Both sides)
Drain hose Connectable
Power source supply Terminal block (Screw fixing type)
Size × Core number 1.5 mm
2
× 4 cores (Including earth cable)
Connection wiring
Connecting method Terminal block (Screw fixing type)
Accessories (included)
Mounting kit, Clean filter (Natural enzyme filter × 1, Photocatalytic washable deodorizing filter × 1)
Optional parts Wired-Remote control
Notes (1) The data are measured at the following conditions.
Model SRK71CF-BP (Indoor unit)
SRC71CF-BP (Outdoor unit)
(2) The operation data are applied to the 220V districts respectively.
(3) The refrigerant quantity to be charged includes the refrigerant in 7 m connecting piping.
(Purging is not required even in the short piping.)
If the piping length is longer, when it is 7 to 25m, add 25g refrigerant per meter.
Refrigerant
piping
Compressor: overheat protection, Frost protection, Serial signal error protection, Indoor fan motor error
protection
(220V)
Item Indoor air temperature Outdoor air temperature
Standards
Operation DB WB DB WB
Cooling
27ºC 19ºC 35ºC 24ºC ISO-T1, JIS C9612
29ºC 19ºC 46ºC 24ºC
ISO-T3, SASO 385/386
The piping length is 7.5m.
ISO-T1
(JIS)
ISO-T3
(SASO)