Specifications
-
57
-
No.
1
2
3
4
Z
Y
X
Z
Y
X
See the super link adapter’s manual concerning connections to the super link adapter.
1Cut jumper wire (J2) on the circuit board.
Caution: This device cannot be used together with the wireless remote
control which is supplied with the indoor unit.
2Connections between the interface and super link adapter
3Fasten the super link adapter cable with clamps.
CNT connector functions
Super link adapter connection
Jumper wire (J2)
Super link
adapter
Super link
adapter
terminal block
Interface side
Within 200 m 0.5 mm
2
× 3 cores
Within 300 m 0.75 mm
2
× 3 cores
Within 400 m 1.25 mm
2
× 3 cores
Within 600 m 2.0 mm
2
× 3 cores
Shielded wire
Vinyl cabtyre round cord
Vinyl cabtyre round cable
Vinyl insulated wirevinyl sheathed cable for control
Z terminal: black wire
Y terminal: white wire
X terminal: red wire
Names of recommended signal wires
Turning the contacts ON/OFF, the off/running status of the air conditioner can be monitored from the External control unit (remote display).
1Connect a locally procured remote control
unit to the CNT terminal.
2In case of the pulse input, cut off the
jumper wire “J1” on the main unit PCB.
3When setting at Operation
permission/prohibition Mode, cut off the
jumper wire “J3”.
䢇 X
R1~4 are for the DC 12V relay
䢇 XR5 is a DC 12/24 or AC 220~240V relay
䢇 CNT connector (local) maker, model
Pulse input
(J1 cut)
Pulse input
(J1 cut)
Input
Output
Operation output
Heating output
Malfunction output
ON output (XR1 = ON) during air conditioner operation
ON output (X
R2 = ON) during heating operation
ON output (X
R3 = ON) during compressor operation
ON output (X
R4 = ON) during an abnormal stop
Content
Jumper wire (J3)
In the operation permited/prohibited mode, remote control operations are allowed only when the input is turned ON.
X
R1
X
R5
X
R1
X
R2
X
R3
X
R4
1
2
3
4
5
6
X
R2
X
R3
X
R4
X
R5
CNT connector
0.3 mm
2
(Keep the distance between the relay and the CNT terminal within 2 m.)
Common
Power supply
DC 12/24 V
or
AC 220~240V
Output 1
Output 2
Output 3
Output 4
Input
Jumper wire (J1)
Connector
Terminals
Molex
Molex
5264-06
5263T
X
R5
Air conditioner ON/OFF is inverted
depending on the pulse signal at OFF ON.
X
R5
Air conditioner ON/OFF is inverted
depending on the pulse signal at OFF ON.
Output 1
Output 2
Output 3
Output 4
Compressor
operation output
Remote
control input
Input
Level input
(At shipment)
Level input
(At shipment)
External control
(At shipment)
External control
(At shipment)
Operation permission
/prohibition (J3 cut)
Operation permission
/prohibition (J3 cut)
X
R5
X
R5
OFF
ON
ON
OFF
Air conditioner OFF
Air conditioner OFF
X
R5
X
R5
OFF
ON
ON
OFF
Air conditioner ON
Air conditioner OFF