Technical data
2
FDT - 8 Series (Cassette)
FDC - 6 Series (Outdoor)
SYSTEM REFERENCE 3086 3086 (3ph) 4086 5086
PERFORMANCE Note
Cooling performance nom. (1) KW 7.10 7.10 10.20 12.50
Cooling UK Conditions (2) KW 6.82 6.82 9.79 12.00
Sensible Cooling UK (3) KW 5.05 5.05 7.05 8.28
Heating Performance (HP only) KW 7.30 7.30 10.50 12.80
ELECTRICAL DATA
System Power connection Mains to outdoor unit first. Interconnecting wiring - 3 wires + Earth, for cooling, 5 wires + Earth, for Heat Pump
Run current - cooling A 16.3 6.0/ph 7.5/ph 10.0/ph
Start current max. L R A A 89 43/ph 45/ph 68/ph
Recommended Fuse Rating (Local) (5) A 30 15/ph 15/ph 20/ph
INDOOR UNIT ref: FDT 8 Series FDT308 FDT308 FDT408 FDT508
Dimension - Unit H x W x D mm 260 x 840 x 840 320 x 840 x 840
Net Weight kg 30 30 34 36
Fan Specification Turbo Fan x 1
Motor Rating W 30 x 1 30 x 1 80 x 1 130 x 1
Airflow (6) High / low speed m
3
/s 0.28 / 0.20 0.28 / 0.20 0.43 / 0.31 0.46 / 0.33
Sound level at 1 metre below high / low dBA 41 / 35 41 / 35 48 / 40 49 / 43
Safety Control Internal thermostat for fan motor. Frost protection thermostat.
Condensate Lift Pump – Max lift (7) mm 700 700 700 700
Condensate Connection Size o.d. mm 25 25 25 25
Fresh Air Inlet facility Inlet facility on all models
Exhaust Air Duct facility Branch duct facility on all models
Refrigerant Control Capillary tube.
Pipe Termination Sizes o.d. ins 5/8 5/8 3/4 3/4
o.d. ins 3/8 3/8 3/8 3/8
Filter Long life filter x 1(Washable)
Remote Control (wired) Multi function wired controller with alternative temperature sensor
OUTDOOR UNIT ref: FDC
 6
FDC306 FDC306
(
3
p
h
)
FDC406
(
3
p
h
)
FDC506
(
3
p
h
)
Dimension - Unit H x W x D mm 844 X 950 X 340 1250 X 950 X 340
Net Weight kg 69 69 86 91
Fan Specification
Propeller Fan x 1 Propeller Fan x 2
Motor Rating W 60
X
1 60
X
1 60
X
2 60
X
2
Sound level at 1 metre in front dBA 56 56 57 59
Refrigerant R22 ONLY
Refrigerant factory charge kg 1.3 1.3 1.6 2.3
REFRIGERANT PIPING
Pipe Termination Sizes o.d. ins 5/8 5/8 3/4 3/4
o.d. ins 3/8 3/8 3/8 3/8
Maximum pipe run m 30 30 30 30
Max height diff. Outdoor unit above / below m 15 15 15 15
NOTES
 1
 Nominal cooling rated at ISO-A, JIS B8616  Outdoor:  35
o
C DB / 24
o
C WB Indoor: 27
o
C DB / 19
o
C WB
 2 U K Cooling  Outdoor: 30
o
C DB / 20
o
C WB  Indoor: 23
o
C DB / 17
o
C WB
 3
 Sensible Cooling calculated at UK conditions, at standard air volume.
 4 Heating Performance rated at: Outdoor   7
o
C DB / 6
o
C WB Indoor:  20
o
C DB
 5
Power supply to outdoor unit. Use motor rated fuse or MCB. Requirement may vary depending on site conditions.
 6
 CEN & HEN = 1ph CES & HES = 3ph.
 7
 Condensate lift measured from ceiling line.
 8
 Cooling and heat pump systems available in R22 models 2088 & 2588.
Technical data for R22 and R407C Systems