Technical data

26
OPTION
Superlynk Connection - FD Series Split Systems
This board is used when conducting control of the single package (wired remote controller unit) 8-type series using a Super
lynk option (SLA-1-E, SLA-2A-E, etc).
(1) Functions
(a) Transmits the settings from the Super lynk option to the indoor units.
(b) Returns the priority indoor unit data in response to a data request from the Super lynk option.
(c) Inspects the error status of connected indoor units and transmits the inspection codes to the Super lynk option.
(d) A maximum of 16 units can be controlled (if in the same operation mode).
(2) Wiring connection diagram
SL E BOARD
A
B
X
Y
Z
X
Y
Z
Blue
Blue
Red
White
Black
Master/Slave address
Network address [00] ~ [47]
Connection to super lynk
(total length of wires: 1000 m maximum)
0.75 ~ 2.0 mm
2
2-core
Connection to the terminal block for remote control (polar)
(total length of wires: 600 m maximum)
No. Name of the recommended signal wire
1 Shielding wire
2 Vinyl cabtire round cord
3 Vinyl cabtire round cable
4 Control vinyl insulated, vinyl sheath cable
Master/Slave Address
SW 3-1
ON Master
OFF Slave
Shielding wires:
100 ~ 200 m ................. 0.5 mm
2
× 3-core wires
~ 300 m ................. 0.75 mm
2
× 3-core wires
~ 400 m ................. 1.25 mm
2
× 3-core wires
~ 600 m ................. 2.0 mm
2
× 3-core wires
Make sure to ground one side only of the shielding wire.
(a) Set the super lynk network address with SW1 (10-position) and SW2 (1-position).
(b) Without a remote control (no wired remote control and no wireless remote controll), set SL E board SW3-1 to ON (Master).
Outdoor unit
Internal/external Crossing
Indoor unit
Remote control
SL E Board
Network
options
X Y Z
X Y Z
X Y Z
A B
A B
Outdoor unit
Internal/external Crossing
Indoor
unit
Indoor
unit
Indoor
unit
Indoor
unit
RR
SL E
Board
Network
options
Outdoor unit
Internal/external Crossing
Indoor
unit
Indoor
unit
Indoor
unit
Indoor
unit
Indoor
unit
Indoor
unit
Indoor
unit
RR
SL E
Board
Outdoor unit
Internal/external Crossing
RR
SL E
Board
Network
options
Outdoor unit
Internal/external Crossing
Indoor
unit
Indoor
unit
SL E
Board
Network
options
Outdoor unit
Internal/external Crossing
Indoor
unit
Indoor
unit
SL E
Board
Network
options
Wireless Kit
Wireless
remote control
Basic Connections
Plural Controls by Multiple Remote Controls.
Mixture of Multiple Units
Transmit the information of plural “Master”
units to the network.
Transmit the abnormalities of the “Slave” units
to the network.
s Setting the plural “Master/Slave” units with the dip SW of the
printed circuit board.
s Setting the “Master/Slave” remote controls with the dip SW of the
remote control board.
Without Remote Control
Plural Controls by Multiple Remote Controls.
Mixture of Multiple Units
Wireless Kit
s Set “00” ~ “47” with the address SW (rotary SW)
of the SL E board.
s Set the SL E board dip
SW to “Master” SW3-1
ON.
The network option
SLA-1-E is not allowed
(This will disturd
switching of the
operation mode)