Technical data
26
OPTION
Superlynk Connection - FD Series Split Systems
This board is used when conducting control of the single package (wired remote controller unit) 8-type series using a Super
lynk option (SLA-1-E, SLA-2A-E, etc).
(1) Functions
(a) Transmits the settings from the Super lynk option to the indoor units.
(b) Returns the priority indoor unit data in response to a data request from the Super lynk option.
(c) Inspects the error status of connected indoor units and transmits the inspection codes to the Super lynk option.
(d) A maximum of 16 units can be controlled (if in the same operation mode).
(2) Wiring connection diagram
SL E BOARD
A
B
X
Y
Z
X
Y
Z
Blue
Blue
Red
White
Black
Master/Slave address
Network address [00] ~ [47]
Connection to super lynk
(total length of wires: 1000 m maximum)
0.75 ~ 2.0 mm
2
 2-core
Connection to the terminal block for remote control (polar)
(total length of wires: 600 m maximum)
No. Name of the recommended signal wire
1 Shielding wire
2 Vinyl cabtire round cord
3 Vinyl cabtire round cable
4 Control vinyl insulated, vinyl sheath cable
Master/Slave Address
SW 3-1
ON Master
OFF Slave
Shielding wires:
100 ~ 200 m .................  0.5 mm
2
 × 3-core wires
~ 300 m .................  0.75 mm
2
 × 3-core wires
~ 400 m .................  1.25 mm
2
 × 3-core wires
~ 600 m .................  2.0 mm
2
 × 3-core wires
● Make sure to ground one side only of the shielding wire.
(a) Set the super lynk network address with SW1 (10-position) and SW2 (1-position).
(b) Without a remote control (no wired remote control and no wireless remote controll), set SL E board SW3-1 to ON (Master).
Outdoor unit
Internal/external Crossing
Indoor unit
Remote control
SL E Board
Network
options
X Y Z
X Y Z
X Y Z
A B
A B
Outdoor unit
Internal/external Crossing
Indoor
unit
Indoor
unit
Indoor
unit
Indoor
unit
RR
SL E
Board
Network
options
Outdoor unit
Internal/external Crossing
Indoor
unit
Indoor
unit
Indoor
unit
Indoor
unit
Indoor
unit
Indoor
unit
Indoor
unit
RR
SL E
Board
Outdoor unit
Internal/external Crossing
RR
SL E
Board
Network
options
Outdoor unit
Internal/external Crossing
Indoor
unit
Indoor
unit
SL E
Board
Network
options
Outdoor unit
Internal/external Crossing
Indoor
unit
Indoor
unit
SL E
Board
Network
options
Wireless Kit
Wireless 
remote control
Basic Connections
Plural Controls by Multiple Remote Controls.
Mixture of Multiple Units
• Transmit the information of plural “Master”
units to the network.
• Transmit the abnormalities of the “Slave” units
to the network.
s Setting the plural “Master/Slave” units with the dip SW of the
printed circuit board.
s Setting the “Master/Slave” remote controls with the dip SW of the
remote control board.
Without Remote Control
Plural Controls by Multiple Remote Controls.
Mixture of Multiple Units
Wireless Kit
s Set “00” ~ “47” with the address SW (rotary SW)
of the SL E board.
s Set the SL E board dip
SW to “Master” SW3-1
ON.
❈ The network option
SLA-1-E is not allowed
(This will disturd
switching of the
operation mode)