Technical data

SYSTEM REFERENCE 2088 2588 3086 3086
(
3
p
h
)
3088 3088
(
3
p
h
)
PERFORMANCE
Cooling performance nom. (1) KW 4.85 5.70 7.10 7.10 7.10 7.10
Cooling U K Conditions (2) KW 4.66 5.47 6.82 6.82 6.82 6.82
Sensible Cooling UK (3) KW 3.41 3.83 5.05 5.05 5.05 5.05
Heating Performance (HP only) KW 5.40 6.10 7.30 7.30 8.00 8.00
ELECTRICAL DATA
System Power connection Mains to outdoor unit first. Interconnecting wiring - 3 wires + Earth, for cooling, 5 wires plus + Earth, for Heat Pump
Run current - cooling A 8.2 9.3 15.5 5.2/ph 13.8 5.4/ph
Start current max. L R A A 44 51 89 43/ph 95 45/ph
Recommended Fuse Rating (Local) (5) A 20 30 30 15/ph 30 20/ph
INDOOR UNIT ref: FDT 8 Series FDKN208 FDKN258 FDKN308 FDKN308 FDKN308 FDKN308
TECHNICAL DATA
Dimension - Unit H x W x D mm 275 x 790 x 179 298 x 940 x 196 298 x 1155 x 196
Net Weight kg 10 11 13.5 13.5
Fan Specification Tangential Fan x 1
Motor Rating W 26 x 1 40 x 1 40 x 1 40 x 1 40 x1 40 x 1
Airflow (6) High / low speed m
3
/s 0.27 / 0.16 0.28 / 0.18 0.35 / 0.25 0.35 / 0.25 0.35 / 0.25 0.35 / 0.25
Sound Level at 1 m below/1m front - hi/lo dBA 45 / 38 45 / 38 46 / 40 46 / 40 46 / 40 46 / 40
Safety Control Internal thermostat for fan motor. Frost protection thermostat.
Condensate Lift Pump – Max lift mm N/A
Condensate Connection Size o.d. mm 16 16 16 16 16 16
Fresh Air Inlet / Exhaust Air facility N/A
Refrigerant Control Capillary tube.
Pipe Termination Sizes o.d. ins 5/8 5/8 5/8 5/8 5/8 5/8
o.d. ins 1/4 3/8 3/8 3/8 3/8 3/8
Filter Long life filter x 2 (Washable) Long life filter x 3 (Washable)
Remote Control (wireless infra-red) Multi function hand held controller, supplied with wall bracket
OUTDOOR UNIT ref: FDC 8 FDC208 FDC258 FDC306 FDC306
(
3
p
h
)
FDC308 FDC308
(
3
p
h
)
TECHNICAL DATA
Dimension - Unit H x W x D mm 690
X
880
X
290 845
X
880
X
340 844
X
950
X
340 845
X
880
X
340
Net Weight kg 49 55 69 74
Fan Specification Propeller Fan x 1
Motor Rating W 55 X 1 55 X 1 60 X 1 55 X 1
Sound level at 1 metre in front dBA 52 52 56 56 52 52
Refrigerant type R22
OR
R407C (8 S
ERIES
)
Refrigerant factory charge R22 / R407C kg 0.98 / 0.98 1.1 / 1.2 1.3 / N/A 1.3 / N/A 1.4 / 1.75 1.4 / 1.75
REFRIGERANT PIPING
Pipe Termination Sizes o.d. ins 5/8 5/8 5/8 5/8 3/4 3/4
o.d. ins 1/4 3/8 3/8 3/8 3/8 3/8
Maximum pipe run m 30 30 30 30 50 50
Max height diff. Outdoor unit above / below m 15 / 15 15 / 15 15 / 15 15 / 15 30 / 15 30 / 15
NOTES
1 Nominal cooling rated at ISO-A, JIS B8616 Outdoor: 35
o
C DB / 24
o
C WB Indoor: 27
o
C DB / 19
o
C WB
2
U K Cooling Outdoor: 30
o
C DB / 20
o
C WB Indoor: 23
o
C DB / 17
o
C WB
3
Sensible Cooling calculated at UK conditions, at standard air volume.
4
Heating Performance rated at: Outdoor 7
o
C DB / 6
o
C WB Indoor: 20
o
C DB
5 Recommendations are for supply to outdoor unit. Use motor rated fuse or MCB. Requirement may vary depending on site conditions.
CEN & HEN = 1ph CES & HES = 3ph.
Cooling only systems available in R22 models 2088 & 2588. Cooling only available with R22 FDC 6 Series outdoor units, and all R407C FDC 8 Series.
17
FDKN - 8 Series (cassette)
FDC - 6 & 8 Series (outdoor)
6
7
13.5 13.5