Technical data
12
FDEN - 8 Series (ceiling)
FDC - 8 Series (outdoor)
SYSTEM REFERENCE 2088 2588 3088 3088
(
3
p
h
)
4088 5088
PERFORMANCE
Cooling performance nom. (1) KW 5.00 5.70 7.10 7.10 10.00 12.50
Cooling U K Conditions (2) KW 4.80 5.47 6.82 6.82 9.60 12.00
Sensible Cooling UK (3) KW 3.51 4.05 5.05 5.05 6.91 8.28
Heating Performance (HP only) KW 5.40 6.10 8.00 8.00 11.20 14.00
ELECTRICAL DATA
System Power connection Mains to outdoor unit first. Interconnecting wiring - 3 wires + Earth, for cooling, 5 wires plus + Earth, for Heat Pump
Run current - cooling A 8.2 9.4 13.9 5.1/ph 7.6/ph 9.3/ph
Start current max. L R A A 44 51 95 45/ph 53/ph 74/ph
Recommended Fuse Rating (Local) (5) A 20 30 30 15/ph 15/ph 20/ph
INDOOR UNIT ref: FDEN 8 Series FDEN208 FDEN258 FDEN308 FDEN308 FDEN408 FDEN508
Dimension - Unit H x W x D mm 184 x 1000 x 650 184 x 1260 x 650 239 x 1260 x 650 239 x 1470 x 650
Net Weight kg 22 27 27 30 34 40
Fan Specification Centrif. fan x 2 Multi-blade centrifugal fan x 4
Motor Rating W 40 x 1 25 x 2 35 x 2 35 x 2 35 + 55 55 x 2
Airflow (6) High / low speed m
3
/s 0.23 / 0.16 0.26 / 0.17 0.28 / 0.19 0.28 / 0.19 0.43 / 0.31 0.46 / 0.33
Sound level at 1 metre below high / low dBA 43 / 38 44 / 39 45 / 39 45 / 39 49 / 43 50 / 44
Safety Control Internal thermostat for fan motor. Frost protection thermostat.
Condensate Lift Pump – Max lift mm N / A
Condensate Connection Size o.d. mm 20 20 20 20 20 20
Fresh Air Inlet facility Aperture required in rear section of unit – max 10% of unit air volume
Exhaust Air Duct facility N / A
Refrigerant Control Capillary tube.
Pipe Termination Sizes o.d. ins 5/8 5/8 5/8 5/8 3/4 3/4
o.d. ins 1/4 3/8 3/8 3/8 3/8 3/8
Filter Polypropylene net x 2 (Washable) Polypropylene net x 3 (Washable)
Remote Control (wireless infra red) Multi function hand held controller, supplied with wall bracket
OUTDOOR UNIT ref: FDC 8 FDC208 FDC258 FDC308 FDC308
(
3
p
h
)
FDC408 FDC508
TECHNICAL DATA
Dimension - Unit H x W x D mm 690 X 880 X 290 845 X 880 X 340 1050X 920 X 340 1250 X 920 X 340
Net Weight kg 49 55 74 74 90 101
Fan Specification
Pro
p
eller Fan x 1 Pro
p
eller Fan x 2
Motor Rating W 55
X
1 55
X
1 55
X
1 55
X
1 40
X
2 65
X
2
Sound level at 1 metre in front dBA 52 52 52 52 54 55
Refrigerant type R22
OR
R407C
Refrigerant factory charge R22 / R407C kg 0.98 / 0.98 1.1 / 1.2 1.4 / 1.75 1.4 / 1.75 1.7 / 2.12 1.9 / 2.58
REFRIGERANT PIPING
Pipe Termination Sizes o.d. ins 5/8 5/8 5/8 5/8 3/4 3/4
o.d. ins 1/4 3/8 3/8 3/8 3/8 3/8
Maximum pipe run m 30 30 50 50 50 50
Max height diff. Outdoor unit above / below m 30 / 15 30 / 15 30 / 15 30 / 15 30 / 15 30 / 15
NOTES 1 Nominal cooling rated at ISO-A, JIS B8616 Outdoor: 35
o
C DB / 24
o
C WB Indoor: 27
o
C DB / 19
o
C WB
2 U K Cooling Outdoor: 30
o
C DB / 20
o
C WB Indoor: 23
o
C DB / 17
o
C WB
3
Sensible Cooling calculated at UK conditions, at standard air volume.
4
Heating Performance rated at: Outdoor 7
o
C DB / 6
o
C WB Indoor: 20
o
C DB
5
Recommendations are for supply to outdoor unit. Use motor rated fuse or MCB. Requirement may vary depending on site conditions.
6 CEN & HEN = 1ph CES & HES = 3ph.
8
Cooling only systems available in R22 models 2088 & 2588. Cooling only available with R22 FDC 6 Series outdoor units, and all R407C FDC 8 Series.
Technical data for R22 and R407C Systems