Specifications

575
FDR-H
(7) Installation work for air outlet ducts
Calculate the draft and external static pressure and select the length, shape and blowout.
A Blowout duct
¡ 2-spot, 3-spot and 4-spot with φ 200 type duct are the standard specifications. Determine the number of spots based on
following table.
Notes (1) Shield the central blowout hole for 2-spot.
(2) Shield the blowout hole around the center for 3-spot.
¡ Limit the difference in length between spots at less than 2 : 1.
¡ Reduce the length of duct as much as possible.
¡ Reduce the number of bends as much as possible. (Corner R should be as larger as possible.)
¡ Use a band, etc. to connect the main unit and the blowout duct flange.
¡ Conduct the duct installation work before finishing the ceiling.
(8) Connection of suction, exhaust ducts
(a) Duct connecting position
i) Fresh air inlet
¡ Inlet can be selected from the side or rear faces depending on the working conditions.
¡ Use the rear fresh air inlet when the simultaneous intake and exhaust is conducted. ( Side inlet cannot be used.)
ii) Exhaust (Make sure to use also the suction.)
Use the side exhaust port.
Blowout duct
(Optional or marketed item)
Air conditioner main unit.
Ceiling surface
Suction hole
(Canvas panel)
Suction hole
(Silent panel)
Heat insulation
A
Special blowout
(Option)
Canvas duct
(Option)
B
FDR258,308FDR208 FDR408,508
2~3-spot
(1)
2-spot 3~4-spot
(2)
Bad example Bad example Good example
Side fresh air inlet
Rear fresh air inlet
Fig. 1 Fig. 2
State seeing from top of unit
Exhaust
port