Specifications
556
FDR-H
Indoor unit
Outdoor unit
Outdoor unit
Outdoor unit
Equipped
unit
Thermistor
(Th
I-A)
Heat exchanger
Liquid line
(ø9.52)
Strainer Strainer
Compressor
Accumlator
StrainerStrainer
Thermistor
(Th
I-R)
Service valve
(Flare connecting)
Capillary tube
Capillary tube
High Pressure
regulator valve
Defrost
Thermostat
Check joint
Heat
exchanger
4way valve
High pressure switch
(For fan motor control)
Service valve
(Flare connecting)
Check joint
Check joint
Gas line
(ø19.05)
(23DH)
Cooling cycle
Heating cycle
Indoor unit
Outdoor unit
Models FDR408HES-A, 508HES-A
Preset point of the protective devices
Parts name Mark
Thermistor
(for protection over-
loading in heating)
Thermistor
(for frost prevention)
Thermistor
(for detecting dis-
charge pipe temp.)
Thermistor
(for detecting heat
exchange temp.)
High pressure switch
(for controlling FM0)
OFF 68˚C
ON 61˚C
ThI-R
Tho-D
Tho-R
63H2
FDR208~508 (FDC208~508 type)
OFF 2.5˚C
ON 10˚C
OFF 135˚C
ON 90˚C
OFF 70˚C
ON 60˚C
OFF 2.5MPa (25.5 Kgf/cm
2
)
ON 2.06MPa (21 kgf/cm
2
)
Parts name Mark
Thermistor
(for protection over-
loading in heating)
Thermistor
(for frost prevention)
Defrost thermostat
High pressure switch
(for controlling FMo)
OFF 68˚C
ON 61˚C
Equipped
unit
THI-R
23DH
2
23DH
1
63H2
Indoor unit
Outdoor unit
Outdoor unit
FDR308~508 (FDC306~506 type)
OFF 2.5˚C
ON 10˚C
OFF 12˚C
ON -6˚C
OFF 2.5MPa (25.5 Kgf/cm
2
)
ON 1.86MPa (19 kgf/cm
2
)