Specifications
-
88
-
Red LED
Green LED
4 time flashes
1 time flash
Outdoor unit
Did 63H1,operate?
NO
Defective outdoor unit PCB
Replacement (Defective 63H1,
input circuit)
YES
At 63H1 operation
1. During cooling
• Is the outdoor unit fan motor operating?
• Is there no short circuit air circulation for thr outdoor
unit?
• Is there sufficient space for air inlet & outlet?
2. During heating
• Is the gas side service valve fully opened?
• Is the indoor unit heat exchanger thermistor detached
from the detector case?
• Is the filter clogged?
• Is the outdoor unit fan controlled by due to defective
63H2?
3. During colling/heating
• Is the refrigerant overcharge?
At 49C operation
During cooling/heating
• Isn't there insufficient refrigerant?
(Isn't there gas leakage?)
• Isn't there a missing phase (
L1
or
L2
phase)?
63H1, 49C operation
Red LED
Green LED
5 time flashes
1 time flash
Outdoor unit
Failure to open the service valve
This abnormality will be indicated only when the compressor is ON for the time after turning on the power. (Refer to page 51)
6
7