Specifications

-
71
-
(d) In the case where the unit is exposed to strong wind.
Face the unit air outlet at a 90 ˚angle from the direction of the wind.
(c) Securing outdoor unit (in the case of exposure to severe weather conditions)
Fix the unit in the following way.
Use overturning prevention brackets.
Rig with wires.
(Use rigging wires that are resistant to corrosion and sufficient in strengh.
For example SUS304-W1, wire thickness 2.9 mm)
Ring with wires
Fix the unit using achor bolts
(2) Carry-in and installation of unit
Pay sufficient attention to the carry-in and moving work of the unit, and always execute work by two persons or more.
(a) Carry-in
1) When carrying-in the unit, carry it in as packed condition to the installa-
tion site as near as possible.
2) If you are compelled to carry-in the unit unpacked condition, lift the unit
by the rope using a nylon sling or applying protection plates so that the
unit is not marred.
CAUTION
¡ Rope the unit taking the discrepancy of center of gravity into consideration.
Hanging hook
(b) Bolt securing position
Make the width
wide.
1) Use anchor bolts (M10) to secure the unit's legs.
2) Securely install the unit so that it dose not fall over during earth-
quakes or strong winds, etc.
3) Refer to the above illustrations for information regarding con-
crete foundations.
4) Install the unit in a level area. (With a gradient of 1/100 or less.)
Anchor bolt
position
(4 locations)
(Service panel side)
Fasten with a
bolt (M10).
Sink the
foundation
deeply.
Unit: mm