Specifications

-
65
-
(4) Drain piping
(a) Drain piping should always be in a downhill grade (1/50-1/100) and avoid riding across an elevation or makeing traps.
(b) When connecting the drain pipe to the unit, pay suffcient attention not to apply excess force to the piping on the unit side.
Also, fix the piping at a point as close as possible to the unit.
(c) For drain pipe, use hard PVC general purpose pipe VP-25 which can be purchased
locally. When connecting, insert a PVC pipe end securely into the drain socket before
tightening securely using the attached drain hose and clamp. Adhesive must not be
used connection of the drain socket and drain hose ( accessory).
(d)When constructing drain piping for several units, position the common pipe about 100 mm below the drain outlet of each unit
as shown in the sketch below. Use VP-30 or thicher pipe for this purpose.
(e) Be sure to provide heat insulation to hard PVC pipes of indoor placement.
(f) Do not ever provide an air vent.
1.5 m ~ 2m
Suspension
bolts
Heat
insulation
A downhill grade
of 1/100 or more
Air vent
Avoid riding across an elevation
Keep free from traps
Do not pipe under water
Drain socket
Level difference part
Drain hose
Joint for VP-25
(local procurement)
Pipe cover (small)[insulation]
(accessory)
Drain socket
Indoor
unit
Clamp
(accessory)
Drain hose
(accessory)
Adhesion
VP-25
(local procurement)
Pipe cover [insulation]
(local procurement)
Pipe cover (large)[insulation]
(accessory)
VP30
A downhill grade of
1/100 or more
Secure the elevation as high as possible
(approx. 100 mm)
Good piping
Improper piping
(b) Tap selection on blower unit.
Taps of on blower unit are set at the standard selection at the shipping from factory. Where the static pressure is raised by
changeing the connection of connectors provided at the flank of control box as shown below.
Standard tap(at shipping)
Red
Blue
Black
Yellow/Green Yellow/Green
Control box side
Motor side
White
Connector white
Red
Blue
White White
High speed tap
Red
Blue
Black
Yellow/Green Yellow/Green
Control box side
Motor side
Red
Connector white
Blue
Models
FDUR208,258
FDUR308,408,508
Static Pressure
Unit : Pa
Standard tap
50
50
High tap
85
130
Black
White White
CAUTION
¡ Taps should not be used under static pressure outside the unit mentioned above. Dew
condensation may occur with the unit and wet the ceiling or furniture.
¡ Do not use under static pressure outside the unit of 50Pa or less. Water drops may be blown
from the diffuser outlet of the unit and wet the ceiling or furniture.