Specifications

-
29
-
Note (1) Refer to page 73 for piping size after branching.
Heat
exchanger
Thermistor
Capillary tube
Thermistor
Cooling cycle
Heating cycle
4way valve
Muffler
Muffler
Capillary tube
Capillary tube
Accumlator
Heat
exchanger
Lower Upper
(Th
O-A)
(Th
I-A)
(Th
I-R)
Thermistor
Service valve
(Brazing)
Branch
pipe
(Brazing)
Branch
pipe
(Brazing)
Branch
pipe (Brazing)
Secondary
branch pipe
High pressure switch(63H2)
(For fan motor control)
High pressure
switch(63H1)
(For protection)
Check valve
Compressor
Service valve
(Flare connecting)
Thermistor (ThO-R)
Strainer
Strainer
Flare connecting
Branch pipe
(Brazing)
First branch pipe
Strainer
Strainer
(ø15.88) (ø15.88)
(ø15.88)
Secondary
branch pipe
(ø9.52)
(ø19.05)
First branch
pipe
(ø19.05)
( )
208 : ø6.35
258 : ø9.52
( )
208 : ø6.35
258 : ø9.52
( )
208 : ø6.35
258 : ø9.52
( )
208 : ø6.35
258 : ø9.52
(ø15.88) (ø15.88)
Heat
exchanger
Thermistor
Capillary tube
Thermistor
(ThI-A)
(Th
I-R)
Branch
pipe
(Brazing)
Branch
pipe (Brazing)
Strainer
Strainer
Flare connecting
Gsa line
808 : ø25.4
1008 : ø28.58
( )
Liquid line
( )
808 : ø12.7
1008 : ø15.88
Strainer
Strainer
Solenoid
Vaive (SV)
Indoor unit
Indoor unit
Indoor unit Indoor unit
(3) Dauble twin type
Models FDCP808HES3,1008HES3
OFF 2.79MPa
ON 2.26MPa
ThI-R
Tho-R
63H2
63H1
Indoor unit
Outdoor unit
Outdoor unit
Preset point of the protective devices
Parts name Mark
Thermistor
(for protection over-
loading in heating)
Thermistor
(for frost prevention)
Thermistor
(for detecting heat
exchange temp.)
High pressure switch
(for controlling FM0)
High pressure switch
(for protection)
OFF 68˚C
ON 61˚C
Equipped
unit
OFF 2.5˚C
ON 10˚C
OFF 70˚C
ON 60˚C
OFF 3.24MPa
ON 2.65MPa
FDCP808HES3, 1008HES3