Specifications

-
12
-
1 Total power input (kW)
(Cooling) 8.20 + 0.23+ 0.27 = 8.70 (kW)
(Heating) 7.78 + 0.23+ 0.27 = 8.28 (kW)
2 Total running current (A)
(Cooling) 13.3 + (1.1+1.4 ×
) 15.0 (A)
(Heating) 12.6 + (1.1 + 1.4 ×
) 14.3 (A)
3 Total power factor (%)
(Cooling) × 100 88 %
(Heating) × 100 88 %
=
.
.
=
.
.
=
.
.
Max. 30m (Outdoor unit is higher)
Max. 15m (Outdoor unit is lower)
Model
Item
Indoor return air temperature
(Upper, lower limits)
Outdoor air temperature
(Upper, lower limits)
Indoor unit atmosphere (behind ceiling)
temperature and humidity
Refrigerant line (one way) length
Vertical height difference between
outdoor unit and indoor unit
Power source voltage
Voltage at starting
Frequency of ON-OFF cycle
ON and OFF interval
Dew point temperature: 28˚C or less, relative humidity: 80% or less
Refer to the selection chart
Max. 10 times/h
Max. 3 minutes
Min. 85% of rating
Rating ± 10%
FDCP808HES3 FDCP1008HES3
=
.
.
2.2 Range of usage & limitations
Item
Model
FDCP808HES3 FDUR308-A FDT508-A
Operation characteristics of each unit
(Cooling/Heating)
Power input (kW)
Running current (A)
8.20/7.78
13.8/12.6
0.23/0.23
1.1/1.1
0.27/0.27
1.4/1.4
Max. 50m
(1)
Difference in height between indoor units
Max. 4m
Note (1) Refer to the next page for details of common pipe length.
3) Total power factor
Total power factor (%) = [Total power input (W) /
3 × Total running current (A) × Power source] × 100
Total operation characteristics = Operation characteristic value of outdoor unit + Operation characteristic value of indoor unit
[Example]
(Conditions) Operation Voltage ········ Indoor unit: 220 V, 50 Hz
Outdoor unit: 380 V, 50 Hz
Operation mode ··········· Cooling and Heating
Unit·······························Outdoor unit: FDCP808HES3 × 1 unit
Indoor unit: FDUR308-A × 1 units, FDT508-A × 1 units
2
3
2
3
8.70 × 1000
3 × 15.0 × 380
8.28 × 1000
3 × 14.3 × 380