Specifications
-
11
-
(c) Calculation of total operation characteristics
Since the operation characteristics of series Multi depend on combination of indoor unit, calculate the total operation
characteristics of the system by using the formulas below according to specifications of each indoor unit or outdoor unit.
1) Total power input
Total power input (kW) = Power input of outdoor unit + ∑ (Power input of indoor unit)
2) Total running current
Total running current (A) = Running current of outdoor unit + [∑ (Running current of indoor unit) × 2/3]
(3) Operation chart
Regarding the operation characteristics of the twin unit of the same model and with the same capacity, please refer to the nameplate
on the equipment.
For any other combinations (Twin, triple or double-twin of different models and different capacities), please calculate based on the
following operaion characteristics. (See page 12.)
(a) Operating characteristic of outdoor unit
Cooling input
Heating input
Cooling running current
Heating running current
Inrush current (L.R.A)
Cooling power factor
Heating power factor
(380 V/415 V)
Item
Model
8.20/8.38
7.78/7.86
13.3/13.5
12.6/12.8
99
94/86
94/85
12.36/12.42
11.22/11.43
19.8/18.9
18.6/17.9
154
95/91
92/89
FDCP808HES3 FDCP1008HES3
kW
A
A
%
Note (1) This packaged air-conditioner is manufactured and tested in conformity with the following standard.
ISO-T1 “UNITARY AIR-CONDITIONERS”
(b) Operating characteristic of indoor unit
Item
Model FDT Series
FDT Series
(220 V/240 V)
Power input (kW)
Running current (A)
0.10/0.11
0.5/0.5
0.11/0.12
0.6/0.6
0.21/0.21
1.2/1.2
0.27/0.27
1.4/1.4
208-A 258-A 308-A 408-A 508-A
Item
Model FDR Series
FDR Series
(220 V/240 V)
Power input (kW)
Running current (A)
0.11/0.120.10/0.11
0.5/0.5
0.15/0.16
0.7/0.7
0.19/0.19
0.9/0.9
0.24/0.24
1.2/1.2
208-A 258-A 308-A 408-A 508-A
Item
Model FDUR Series
FDUR Series
(220 V/240 V)
Power input (kW)
Running current (A)
0.20/0.22
1.0/1.0
0.18/0.19
0.9/0.9
0.23/0.24
1.1/1.3
0.33/0.37
1.5/1.7
0.40/0.45
1.8/2.0
208-A 258-A 308-A 408-A 508-A
Notes (1) This packaged air-conditioner is manufactured and tested in conformity with the following standard.
ISO-T1 “UNITARY AIR-CONDITIONERS”
(2) The values shown in the above table are common to both cooling and heating operations.