(1) Diagnostic information
Special Relay List
Number Name Meaning Explanation
Set by
(When Set)
Corresponding
ACPU
M9
Corresponding
CPU
SM0 Diagnostic errors
OFF : No error
ON : Error
• This relay turns on if an error is detected by diagnostics.
(Also turns on if an error is detected by an annunciator or
the CHK instruction.)
This relay remains on even after the system returns to
normal.
S (Error) New
QnA
Qn(H)
QnPH
QnPRH
Rem
• This relay turns on if an error is detected by diagnostics.
(Also turns on if an error is detected by an annunciator.)
This relay remains on even after the system returns to
normal.
S (Error) New
Q00J/
Q00/Q01
QnU
SM1
Self-diagnostic
error
OFF : No error
ON : Error
This relay turns on if an error is detected by self-
diagnostics. (Remains off if an error is detected by an
annunciator or the CHK instruction.)
This relay remains on even after the system returns to
normal.
S (Error) M9008
QnA
Qn(H)
QnPH
QnPRH
Rem
This relay turns on if an error is detected by self-
diagnostics. (Remains off if an error is detected by an
annunciator.)
This relay remains on even after the system returns to
normal.
S (Error) New
Q00J/
Q00/Q01
QnU
SM5
Error common
information
OFF : No error common
information
ON : Error common
information
• This relay turns on if error common information data
exists when SM0 turns on.
S (Error) New
Rem
SM16
Error individual
information
OFF : No error individual
information
ON : Error individual
information
• This relay turns on if error individual information data
exists when SM0 turns on.
S (Error) New
SM50 Error reset
OFF
ON : Error reset
• Conducts error reset operation. U New
SM60
Blown fuse
detection
OFF : Normal
ON : Module with blown
fuse
• This relay turns on if there is at least one output module
whose fuse has blown.
This relay remains on even after the system returns to
normal.
• Output modules on remote I/O stations are also checked.
S (Error) M9000
Rem
SM61
I/O module verify
error
OFF : Normal
ON : Error
• This relay turns on if the status of the I/O module differs
from that registered at power-on.
This relay remains on even after the system returns to
normal.
• I/O modules on remote I/O stations are also checked.
S (Error) M9002
(2) System information
Special Relay List
Number Name Meaning Explanation
Set by
(When Set)
Corresponding
ACPU
M9
Corresponding
CPU
SM206
PAUSE enable
coil
OFF : PAUSE disabled
ON : PAUSE enabled
• The status changes to PAUSE if this relay is on when the
PAUSE contact turns on.
U M9040
Device test
request
acceptance
status
OFF : Test not executed
ON : Test executed
• This relay turns on when inputs/outputs are forcibly
registered by GX Developer.
S (Request) New Remote
SM213
Clock data read
request
OFF : Ignored
ON : Read request
This relay is turned on to read clock data and store them
as BCD values into SD210 to SD213.
U M9028
Rem
SM250
Max. loaded I/O
read
OFF : Ignored
ON : Read
• When this relay turns on, the largest I/O number among
those of the mounted modules is read into SD250.
U New
QnA
Qn(H)
QnPH
QnPRH
Rem
SM280 CC-Link error
OFF : Normal
ON : Error
• Turns on if a CC-Link error is detected in any of the CC-
Link modules mounted. Turns off when the condition
returns to normal.
S (Status
change)
New
Qn(H)
QnPH
QnPRH
Rem
• Turns on if a CC-Link error is detected in any of the CC-
Link modules mounted. Remains on even after the
condition returns to normal.
S (Error) New QnA