User's Manual

12-52
4010
[MISSING END INS.]
There is no END (FEND) instruction in the
program.
Collateral information
Common Information:Program error location
Individual Information:–
Diagnostic Timing
At power ON/At reset/STOP RUN
Read the common information of the error using a
peripheral device, check error step corresponding
to its numerical value (program error location), and
correct the problem.
RUN:
Off
ERR.:
Flicker
CPU Status:
Stop
QCPU
4020
[CAN'T SET(P)]
The total number of internal file pointers used by
the program exceeds the number of internal file
pointers set in the parameters.
Collateral information
Common Information:Program error location
Individual Information:–
Diagnostic Timing
At power ON/At reset/STOP RUN
Qn(H)
QnPH
QnPRH
QnU
4021
[CAN'T SET(P)]
The common pointer Nos. assigned to files
overlap.
The local pointer Nos. assigned to files overlap.
Collateral information
Common Information:Program error location
Individual Information:–
Diagnostic Timing
At power ON/At reset/STOP RUN
QCPU
4030
[CAN'T SET(I)]
The allocation pointer Nos. assigned by files
overlap.
Collateral information
Common Information:Program error location
Individual Information:–
Diagnostic Timing
At power ON/At reset/STOP RUN
4100
[OPERATION ERROR]
The instruction cannot process the contained data.
Collateral information
Common Information:Program error location
Individual Information:–
Diagnostic Timing
When instruction executed
RUN:
Off/On
ERR.:
Flicker/On
CPU Status:
Stop/
Continue
*1
QCPU
[OPERATION ERROR]
Access error of ATA card occurs by
SP.FREAD/SP.FWRITE instructions.
Collateral information
Common Information:Program error location
Individual Information:–
Diagnostic Timing
When instruction executed
Take measurements against noise.
Reset and restart the CPU module.
When the same error is displayed again, the
ATA card has hardware failure.
(Please consult your local Mitsubishi service
center or representative, explaining a detailed
description of the problem.)
Qn(H)
QnPH
QnPRH
QnU
*11
[OPERATION ERROR]
The file being accessed by other functions with
SP.FWRITE instruction was accessed.
Collateral information
Common Information:Program error location
Individual Information:–
Diagnostic Timing
When instruction executed
Stop the file accessed with other functions to
execute SP.FWRITE instruction.
Stop the access with othrer functions and the
SP.FWRITE instructuion to execute at same
time.
QnU
*11
Error
Code
(SD0)
Error Contents and Cause Corrective Action
LED Status
CPU Status
Corresponding
CPU
*1 CPU operation can be set in the parameters at error occurrence. (LED indication varies.)
*11 The Universal model QCPU except the Q00UJCPU, Q00UCPU, and Q01UCPU.