User's Manual

12-49
1
2
3
12
6
6
7
8
12.1 Error Code List
12.1.5 Error code list (3000 to 3999)
3302
[SP. PARA ERROR]
The intelligent function module's refresh parameter
are abnormal.
Collateral information
Common Information:File name
Individual Information:Parameter number
*2
Diagnostic Timing
At power-On/ At reset/ STOP RUN/
At writing to progurammable controller
Check the parameter setting.
RUN:
Off
ERR.:
Flicker
CPU Status:
Stop
QCPU
3303
[SP. PARA ERROR]
In a multiple CPU system, the automatic refresh
setting or other parameter setting was made to the
intelligent function module under control of another
station.
Collateral information
Common Information:File name/ Drive name
Individual Information:Parameter number
Diagnostic Timing
At power-On/ At reset/ STOP RUN/
At writing to progurammable controller
Delete the automatic refresh setting or other
parameter setting of the intelligent function
module under control of another CPU.
Change the setting to the automatic refresh
setting or other parameter setting of the
intelligent function module under control of the
host CPU.
Q00/Q01
*1
Qn(H)
*1
QnPH
QnU
*10
3400
[REMOTE PASS. ERR.]
The head I/O number of the target module of the
remote password is set to other than 0
H to 0FF0H.
Collateral information
Common Information:–
Individual Information:–
Diagnostic Timing
At power ON/At reset/STOP RUN
Change the head I/O number of the target module
to be within the 0
H to 0FF0H range.
Qn(H)
*1
QnPH
QnPRH
QnU
*7
[REMOTE PASS. ERR.]
The head I/O number of the target module of the
remote password is set to other than 0
H to 07E0H.
Collateral information
Common Information:–
Individual Information:–
Diagnostic Timing
At power ON/At reset/STOP RUN
Change the head I/O number of the target module
to be within the 0
H to 07E0H range.
Q02U
[REMOTE PASS. ERR.]
The head I/O number of the target module of the
remote password is outside the following range.
Q00JCPU: 0
H to 1E0H
Q00CPU/Q01CPU: 0H to 3E0H
Collateral information
Common Information:–
Individual Information:–
Diagnostic Timing
At power ON/At reset/STOP RUN
Change the head I/O number of the target module
of the remote password for the number within the
following range.
•Q00JCPU: 0
H to 1E0H
Q00CPU/Q01CPU: 0H to 3E0H
Q00J/Q00/Q01
*1
Error
Code
(SD0)
Error Contents and Cause Corrective Action
LED Status
CPU Status
Corresponding
CPU
*1 The function version is B or later.
*2 Parameter No. is the value gained by dividing the head I/O number of parameter in the intelligent function module set by GX Configurator by 10H.
*7 The module whose first 5 digits of serial No. is "09012" or later.