User's Manual

12-44
3102
[LINK PARA. ERROR]
A CC-Link IE controller network parameter error
was detected.
Collateral information
Common Information:File name/ Drive name
Individual Information:Parameter number
Diagnostic Timing
At power ON/At reset/STOP RUN
Correct and write the network parameters.
If the error occurs after correction, it suggests a
hardware fault. (Contact your local Mitsubishi
representative.)
RUN:
Off
ERR.:
Flicker
CPU Status:
Stop
Qn(H)*
7
QnPH*
9
QnPRH*
9
QnU
[LINK PARA. ERROR]
The network module detected a network
parameter error.
A MELSECNET/H network parameter error was
detected.
Collateral information
Common Information:File name/ Drive name
Individual Information:Parameter number
Diagnostic Timing
At power ON/At reset/STOP RUN
QCPU
[LINK PARA. ERROR]
The station No. specified in pairing setting are not
correct.
The stations are not numbered consecutively.
Pairing setting has not been made for the CPU
module at the normal station.
Collateral information
Common Information:File name/ Drive name
Individual Information:Parameter number
Diagnostic Timing
At power ON/At reset/STOP RUN
Refer to the troubleshooting of the network module,
and if the error is due to incorrect pairing setting,
reexamine the pairing setting of the network
parameter.
QnPRH
[LINK PARA. ERROR]
The CC-Link IE controller network module whose
first 5 digits of serial No. is "09041" or earlier is
mounted.
Collateral information
Common Information:File name/ Drive name
Individual Information:Parameter number
Diagnostic Timing
At power ON/At reset/STOP RUN
Mount the CC-Link IE controller network module
whose first 5 digits of serial No. is "09042" or later.
QnU
[LINK PARA. ERROR]
Group cyclic function in CC-Link IE controller
network that does not correspond to group cyclic
function is set.
Collateral information
Common Information:File name/ Drive name
Individual Information:Parameter number
Diagnostic Timing
At power ON/At reset/STOP RUN
Set group cyclic function in function version D or
later of CC-Link IE controller network.
QnU
*9
[LINK PARA. ERROR]
Paring setting in CC-Link IE controller network
modules installed in CPUs except for redundant
CPUs was performed.
Collateral information
Common Information:File name/ Drive name
Individual Information:Parameter number
Diagnostic Timing
At power ON/At reset/STOP RUN
Examine the paring setting for the network
parameter in the control staion.
Q00J/Q00/Q01
Qn(H)
*9
QnPH
*9
QnU
*9
Error
Code
(SD0)
Error Contents and Cause Corrective Action
LED Status
CPU Status
Corresponding
CPU
*7 The module whose first 5 digits of serial No. is "09012" or later.