22. FA TRANSPARENT FUNCTION
22.7 Precautions
(2) When the FA transparent function is used in a bus 
connection
When the FA transparent function is used in a bus 
connection, the following GX Developer functions or 
GX Works2 functions cannot be executed.
The message [The executed function is not supported. 
Please check the manual and other documentation.] is 
displayed on GX Developer or GX Works2.
 When using together with the Multiple-GT11, 
GT10 connection function
When multiple GOTs are connected, the FA transparent 
function is not available even if the RS-232 interface or 
USB interface is used for the connection.
 When PLC power disconnection occurs with 
the FA transparent function being used
While the FA transparent function is being used, if the 
communication between the PLC and the GOT is 
stopped due to PLC power disconnection or a 
disconnection of the communication cable between the 
PLC and the GOT, the GOT waits for timeout against 
the communication request from the peripheral devices 
(GX Developer, etc.), and it takes a few minutes to 
recover the monitoring between the PLC and the GOT.
 When the FA transparent function is used in 
an Ethernet connection
(1) GX Developer function or GX Works2 function
When the FA transparent function is used in an 
Ethernet connection, the following GX Developer 
functions or GX Works2 functions cannot be executed.
The message [The executed function is not supported. 
Please check the manual and other documentation.] is 
displayed on GX Developer or GX Works2.
(2) GOT station monitoring function
When the FA transparent function is used in an 
Ethernet connection, GOT station monitoring function 
cannot be operated.
Therefore, in the cases of [no connection target], [PLC 
power OFF], etc., the monitoring of the GOT delays for 
the timeout time.
Unsupported GX Developer 
functions
Remark
• Remote Reset
• Remote system reset
―
• Remote RUN
• Remote STOP
• Remote PAUSE
• Remote STEP-RUN
• Remote latch clear
• Write clock data
• Clear malfunction log
Inexecutable only when specify all 
stations/groups has been performed.
PC
PC
1st GOT 2nd GOT
RS-232
PC
1st GOT
USB
GX Developer and so on
Online operation
Monitoring
Unsupported GX Developer functions Remark
• Remote Reset
• Remote system reset
―
• Remote RUN
• Remote STOP
• Remote PAUSE
• Remote STEP-RUN
• Remote latch clear
• Write clock data
• Clear malfunction log
Inexecutable only when 
specify all stations/groups 
has been performed.
• Remote password function
• MELSECNET diagnostics
• CC IE Control diagnostics
• CC IE Field diagnostics
• Ethernet diagnostics
(PING test/loopback test with
the Ethernet module (Q series))
―