22.7 Precautions
22.7.1 Precautions common to each 
software
 GOT interface required to use the FA 
transparent function
Connect the personal computer, to which GX 
Developer or any other relevant software has been 
installed, to the RS-232 interface or USB interface of 
the GOT.
When performing the FA transparent function, use 
either RS-232 interface or USB interface of the GOT.
Using both of them to perform the FA transparent 
function concurrently is not allowed.
 Conditions for suspending the FA transparent 
function
The FA transparent function is also suspended when 
any of the following operations, which stop the GOT 
monitor, is performed.
Note that the FA transparent function will not be 
stopped while using the optional function such as the 
Utility display or ladder monitor function.
• When project data is written/read, or when the OS is 
written by GT Designer3
*1
• When the GOT is set up
*1
• When no communication request (online monitor, 
etc.) has been issued from GX Developer for 45 
minutes
*1 A timeout error occurs in GX Developer.
 When GOT monitoring is faulty
The FA transparent function cannot be used in case 
that the GOT monitoring is faulty due to PLC CPU 
errors or faulty communication between the PLC CPU 
and GOT.
When GOT monitoring is faulty, check the following.
(1) Whether the PLC CPU operates normally
Refer to the User's Manual of the PLC CPU you 
use.
(2) Whether the PLC CPU and GOT are connected 
normally
5. BUS CONNECTION
6. DIRECT CONNECTION TO CPU
7. COMPUTER LINK CONNECTION
 When monitoring the PLC CPU from a 
personal computer
When monitoring the PLC CPU from a personal 
computer, the GOT and personal computer refresh the 
display slower.
 Software available for the FA transparent 
function
When multiple kinds of software are activated on one 
personal computer, only one of them is available for 
communications using the FA transparent function.
Do not concurrently perform any communications using 
the FA transparent function.
(Offline operation with each software is available)
Also, do not perform communications with the GOT 
(e.g. downloading project data) from GT Designer3 
during execution of communications using the FA 
transparent function.
 When the FA transparent function is used in 
a bus connection
(1) When multiple GOTs are bus-connected
When multiple GOTs are bus-connected, the FA 
transparent function can be used on each GOT.
However, note that the monitoring performance of each 
GOT slows down as the number of monitoring GOTs 
and personal computers increases.
RS-232
USB
GT Designer3
GX Developer and so on
Online operation
Communication with GOT
PC
RS-232
cable