User's Manual
17 - 4
17. ROBOT CONTROLLER CONNECTION
17.3 GOT Side Settings
*1 Click the [Setting] button and perform the setting in the [GOT 
IP Address Setting] 
screen.
 GT15, GT12
Item Description Range
GOT NET No.
Set the network No. of the GOT.
(Default: 1)
1 to 239
GOT PLC No.
Set the station No. of the GOT.
(Default: 1)
1 to 64
GOT
IP Address
Set the IP address of the GOT.
(Default: 192.168.0.18)
0.0.0.0 to 
255.255.255.255
Subnet Mask
Set the subnet mask for the sub 
network. (Only for connection via 
router)
If the sub network is not used, the 
default value is set.
(Default: 255.255.255.0)
0.0.0.0 to 
255.255.255.255
Default 
Gateway
Set the router address of the default 
gateway where the GOT is 
connected. (Only for connection via 
router)
(Default: 0.0.0.0)
0.0.0.0 to 
255.255.255.255
Ethernet
Download Port 
No.
Set the GOT port No. for Ethernet 
download.
(Default: 5014)
1024 to 5010 to 
5014 to 65534
(Except for 5011, 
5012, 5013 and 
49153)
GOT 
Communication 
Port No.
Set the GOT port No. for the 
connection with the Ethernet module.
(Default: 5001)
1024 to 5010 to 
5014 to 65534
(Except for 5011, 
5012, 5013 and 
49153)
Retry
Set the number of retries to be 
performed when a communication 
timeout occurs.
When receiving no response after 
retries, the communication times out.
(Default: 3times)
0 to 5times
Startup Time
Specify the time period from the GOT 
startup until GOT starts the 
communication with the PLC CPU.
(Default: 3sec)
3 to 255sec
Timeout Time
*1
Set the time period for a 
communication to time out.
(Default: 3sec)
3 to 90sec
Delay Time
Set the delay time for reducing the 
load of the network/destination PLC.
(Default: 0ms)
0 to 10000
(  10ms)