User's Manual
13. CC-Link CONNECTION (INTELLIGENT DEVICE STATION)
13.4 PLC Side Setting
13 - 29
9
MELSECNET/H 
CONNECTION (PLC 
TO PLC NETWORK)
10
MELSECNET/10 
CONNECTION (PLC 
TO PLC NETWORK)
11
CC-Link IE CONTROLLER 
NETWORK 
CONNECTION
12
CC-Link IE FIELD 
NETWORK 
CONNECTION
13
CC-Link CONNECTION 
(INTELLIGENT DEVICE 
STATION)
14
CC-Link 
CONNECTION 
(Via G4)
15
INVERTER 
CONNECTION
16
SERVO AMPLIFIER 
CONNECTION
(b) Station information setting
: Necessary  : As necessary  : Not necessary
*1 Specify the same number of occupied stations as that of the 
GOT.
POINTPOINTPOINT
When changing the network parameter
After writing the network parameter to the PLC CPU,
operate the PLC CPU ether turning OFF and then ON
or resetting.
(2) Setting from sequence program
The parameter is written to the buffer memory, and the 
data link is automatically started when PLC CPU status 
changes from STOP to RUN.
(a) I/O signal of CC-Link module
Control & Communication Link System Master/
Local Module Type AJ61QBT11/A1SJ61QBT11 
User's Manual
(b) Device used by user
(c) Buffer memory settings used in the present 
example
*1 Details for the station data are shown below.
For 1) and 2), set the same station No. and number of station 
occupied as those of the GOT.
For 3), the setting is fixed.
Item Set value
Setting 
necessity at 
GOT 
connection
Station type
Intelligent device station 
(fixed)
Exclusive station count
*1
Exclusive station 1
Reserve/invalid station 
select
No setting
Intelligent buffer select 
(word)
(Use default value)
Device Application
M100, M101 Flag for parameter setting
M102, M103 Flag for data link startup
D0 Number of connected modules
D1 Number of retry
D2 Automatic reconnection station count
D3 Operation specification in the case of CPU failure
D4
Reserved station specification (Station No. 1 to 
Station No. 16)
D5
Error invalid station specification (Station No. 1 to 
Station No. 16)
D6 Station data (first module)
D400 Error code in the case of data link startup failure
Buffer memory 
address
Item Set value
Decimal (Hex)
1(11 (1
H) Number of connected modules 1 (1 module)
2(22 (2
H) Number of retry 3 (3times)
3(33 (3
H)
Automatic reconnection station 
count
1 (1 station)
6(66 (6
H)
Operation specification in the 
case of CPU failure
0 (stop)
16(1016 (10
H)
Reserved station specification 
(Station No. 1 to Station No. 16)
0 (No 
specification)
20(1420 (14
H)
Error invalid station specification
(Station No. 1 to Station No. 16)
0 (No 
specification)
32(2032 (20
H)
Station data (first module)
*1
2101H
1) Station No. (Set the same station No. as that of the GOT)
01
H to 40H: Station No. 1 to Station No. 64
2) Number of stations occupied (Set the number of station 
occupied as that of the GOT)
1
H: Exclusive station 1
2
H: Exclusive station 2
3
H: Exclusive station 3
4
H: Exclusive station 4
3) Station type (2
H: Set it to intelligent device station)
0
H: Remote I/O station
1
H: Remote device station
2
H: Intelligent device station (Incl. local station)
3)
2)
1)
b15 b12 b11 b8 b7 to b0
to to










