User's Manual
13. CC-Link CONNECTION (INTELLIGENT DEVICE STATION)
13.4 PLC Side Setting
13 - 25
9
MELSECNET/H 
CONNECTION (PLC 
TO PLC NETWORK)
10
MELSECNET/10 
CONNECTION (PLC 
TO PLC NETWORK)
11
CC-Link IE CONTROLLER 
NETWORK 
CONNECTION
12
CC-Link IE FIELD 
NETWORK 
CONNECTION
13
CC-Link CONNECTION 
(INTELLIGENT DEVICE 
STATION)
14
CC-Link 
CONNECTION 
(Via G4)
15
INVERTER 
CONNECTION
16
SERVO AMPLIFIER 
CONNECTION
(2) Station information setting
: Necessary  : As necessary  : Not necessary
*1 When the [Mode] of the CC-Link module is set at [Remote 
net - (Ver. 1 mode)], [Remote station points] cannot be set.
*2 Set the same setting as that of the GOT.
POINTPOINTPOINT
When changing the network parameter
After writing the network parameter to the PLC CPU,
operate the PLC CPU ether turning OFF and then ON
or resetting.
 [Controller Setting] of GT Designer3
POINTPOINTPOINT
[Controller Setting] of GT Designer3
For the setting method of [Controller Setting] of GT
Designer3, refer to the following.
13.3.1 Setting communication interface 
(Communication settings)
13.4.5 Connecting to MELSEC-L 
series with CC-Link Ver.2 
compatible
This section describes the settings of the GOT and 
MELSEC-L in the following case of the system 
configuration.
POINTPOINTPOINT
(1) CC-Link module (L Series)
For details of the CC-Link module (L Series), refer 
to the following manual.
MELSEC-L CC-Link System Master/Local 
Module User's Manual
(2) CC-Link function built-in CPU
For details on the CC-Link function built-in CPU, 
refer to the following manual.
MELSEC-L CC-Link System Master/Local 
Module User's Manual
 System configuration
(Example when using CC-Link module (L Series))
Item
*1
Set value
Setting 
necessity at 
GOT 
connection
Station type
Intelligent
device station (fixed)
Exclusive station count
*2
Exclusive station 1
Reserve/invalid station 
select
No setting
Intelligent buffer select 
(word)
(Use default value)
Item Set value
Station No. 1: Station No.1
Transmission Rate 0: Online 156kbps
Mode Ver.1: Remote net (Ver.1 mode)
Expanded Cyclic Single (Use default value)
Number of stations occupied 1 Station
Input for Error Station 0: Clear
Retry 3times (Use default value)
Timeout Time 3sec (Use default value)
Delay Time 0ms (Use default value)
<CC-Link module>
*1
Type : Master station
Station No. : Station No.0
Mode : Remote net (Ver.3 mode)
All connect count : 1
Transmission speed : 156kbps
<GOT>
 (Use the default value for settings other
 than the following.)
Station type : Intelligent device
station
Station No. : Station No.1
Expanded cyclic setting : Single
Number of 
stations occupied
: Exclusive station
Transmission speed : 156kbps
(Use the default value for the settings other than the following.)
■ [Controller Setting] of GT Designer3
■ [Network parameter] of GX Developer