User's Manual
13 - 20
13. CC-Link CONNECTION (INTELLIGENT DEVICE STATION)
13.4 PLC Side Setting
13.4.3 Connecting to CC-Link module 
(Q Series) with Ver.1/Ver.2 
compatibles mixed
This section describes the setting of the GOT and CC-Link 
module (Q Series) with Ver.1/Ver.2 compatibles mixed in 
the following system configuration.
POINTPOINTPOINT
CC-Link module (Q Series)
For details of the CC-Link module (Q Series), refer to
the following manual.
CC-Link System Master/Local Module User's 
Manual QJ61BT11N
 System configuration
*1 The CC-Link module is mounted on the base unit slot 0.
The Start I/O No. of the CC-Link module is set to "0"
POINTPOINTPOINT
When connecting to Q170MCPU
When connected to Q170MCPU, the start I/O No. of
the CC-Link module is set to "70".
 Switch setting of CC-Link module (Q Series)
Set the station number setting switch, transmission 
speed / mode setting switch.
(1) Station number setting switch
: Necessary  : As necessary  : Not necessary
(2) Transmission rate/mode setting switch
: Necessary  : As necessary  : Not necessary
*1 Specify the same transmission speed as that of the GOT.
POINTPOINTPOINT
When the switch setting has been changed
Turn the PLC CPU OFF then ON again, or reset the
PLC CPU.
<CC-Link module>
*1
Type : Master station
Station No. : Station No. 0
Mode  : Remote net (Ver.2 mode)
All connect count  : 2
Transmission speed : 156kbps
<GOT (Ver.1 compatible)> 
(Use default value for settings other than the following.)
Station type : Intelligent device
station
Station No.  : Station No. 1
Number of stations 
occupied
Exclusive station 1:
:Transmission speed 156kbps
(Use default value for settings other than the following.)
<GOT (Ver.2 compatible)> 
(Use default value for settings other
 than the following.)
Station type : Intelligent device
station
Station No.  : Station No. 2
Number of stations 
occupied
 Exclusive station 1:
Expanded cyclic setting Single:
:Transmission speed 156kbps
■ [Controller Setting] of GT Designer3
■ Setting of the CC-Link communication unit
■ Switch setting of CC-Link module (Q Series)
■ [Network parameter] of GX Developer
Station number 
setting switch
Description Set value
Setting necessity 
at GOT connection
Station number 
setting
(master station)
0 (fixed)
Transmission 
rate/mode setting 
switch
Description Set value
Setting necessity 
at GOT connection
Transmission 
rate/
mode setting
(Online: 
156kbps)
*1
0
(1)
(2)
QJ61BT11N
0
5
0
5
0
8
1
2
7
6
5
4
3
STATION 
NO.
X10
X1
MODE
QJ61BT11N
RUN
ERR. 
SD 
MST
L RUN
L ERR.
RD
S MST
NC
DA
DB
NC
SLD
DG
(FG)
C
4