User's Manual
13 - 16
13. CC-Link CONNECTION (INTELLIGENT DEVICE STATION)
13.4 PLC Side Setting
 [Controller Setting] of GT Designer3
(1) When MODEL GT15-J61BT13 CC-Link 
communication unit is used
(2) When MODEL GT15-75J61BT13-Z CC-Link 
communication unit is used
POINTPOINTPOINT
[Controller Setting] of GT Designer3
For the setting method of [Controller Setting] of GT
Designer3, refer to the following.
13.3.1 Setting communication interface 
(Communication settings)
 Setting of the CC-Link communication unit 
(Only when MODEL GT15-75J61BT13-Z 
CC-Link communication unit is used)
POINTPOINTPOINT
Setting of the CC-Link communication unit
For the setting method of the CC-Link communication
unit, refer to the following.
13.3.3 Switch setting (Only when MODEL 
GT15-75J61BT13-Z CC-Link communication 
unit is used)
13.4.2 Connecting to CC-Link 
module (Q Series) with 
Ver.2 compatible
This section describes the settings of the GOT and CC-
Link module (Q Series) in the following case of system 
configuration.
POINTPOINTPOINT
CC-Link module (Q Series)
For details of the CC-Link module (Q Series), refer to
the following manual.
CC-Link System Master/Local Module User's 
Manual QJ61BT11N
 System configuration
*1 The CC-Link module is mounted on the base unit slot 0.
The Start I/O No. of the CC-Link module is set to "0"
POINTPOINTPOINT
When connecting to Q170MCPU
When connected to Q170MCPU, the start I/O No. of
the CC-Link module is set to "70".
Item Set value
Station No. 1: Station No.1
Transmission Rate 0: Online 156kbps
Mode Ver.1: Remote net (Ver.1 mode)
Expanded Cyclic Single (Use default value)
Number of stations occupied 1 Station
Input for Error Station 0: Clear
Retry 3times (Use default value)
Timeout Time 3sec (Use default value)
Delay Time 0ms (Use default value)
Item Set value (Use default value)
Retry 3times
Timeout Time 3sec
Item Set value
Mode setting switch 0: Online (fixed)
Station number setting switch 1: Station No.1
Transmission baudrate setting switch 0: 156kbps
Condition 
setting 
switches
SW1 (Input data status of the 
data link error station)
OFF: Cleared
SW2 (Number of occupied 
stations)
OFF: 1 station
<CC-Link module>
*1
Type : Master station
Station No. : Station No.0
Mode : Remote net (Ver.2 mode)
All connect count : 1
Transmission speed : 156kbps
<GOT>
 (Use the default value for settings other
 than the following.)
Station type : Intelligent device
station
Station No. : Station No.1
Expanded cyclic setting : Single
Number of 
stations occupied
: Exclusive station 1
Transmission speed : 156kbps
(Use the default value for the settings other than the following.)
■ [Communication settings] of GT Designer3
■ Switch setting of CC-Link module (Q Series)
■ [Network parameter] of GX Developer