User's Manual
13 - 12
13. CC-Link CONNECTION (INTELLIGENT DEVICE STATION)
13.4 PLC Side Setting
13.4 PLC Side Setting
The GOT operates as the stations of which are shown 
below in the CC-Link system.
The switch settings and parameter settings of the PLC side 
(CC-Link module) are described in 13.4.1 to 13.4.7.
HINTHINTHINT
Number of stations occupied
The number of stations occupied is setting for 
determining number of link device points (RX/RY/
RWw/RWr) used by the GOT.
To use multiple numbers of link device points in the 
case of cyclic transmission between the GOT and CC-
Link module, set the number of stations occupied as 
the exclusive station 4.
The number of link device points at the exclusive 
station 1 and 4 is shown below.
CC-Link Ver.2
CC-Link Ver.1
Station data Description
Station type
Intelligent device station, Ver.1 intelligent device 
station or Ver.2 intelligent device station
Number of stations 
occupied
Station 1 or Station 4
Model name Refer to
CC-Link
module
(Q Series)
Connecting 
with
Ver.1 
compatible
QJ61BT11, 
QJ61BT11N
13.4.1
Connecting 
with Ver.2 
compatible
QJ61BT11N 13.4.2
Connecting 
with Ver.1/
Ver.2 
compatibles 
mixed
QJ61BT11N 13.4.3
CC-Link module
(QnA Series)
AJ61QBT11, 
A1SJ61QBT11
13.4.6
CC-Link module
(A Series)
AJ61BT11, 
A1SJ61BT11
13.4.7
Link
device
Expanded cyclic setting
Single Double Quadruple Octuple
Exclu
sive 
statio
n 1
Exclu
sive 
statio
n 4
Exclu
sive 
statio
n 1
Exclu
sive 
statio
n 4
Exclu
sive 
statio
n 1
Exclu
sive 
statio
n 4
Exclu
sive 
statio
n 1
Exclu
sive 
statio
n 4
Remote 
input (RX)
32 
points
128 
points
32 
points
224 
points
64 
points
448 
points
128 
points
896 
points
Remote 
output (RY)
32 
points
128 
points
32 
points
224 
points
64 
points
448 
points
128 
points
896 
points
Remote 
register 
(RWw)
4 
points
16 
points
8 
points
32 
points
16 
points
64 
points
32 
points
128 
points
Remote 
register 
(RWr)
4 
points
16 
points
8 
points
32 
points
16 
points
64 
points
32 
points
128 
points
Link device
Number of stations occupied
Exclusive station Exclusive station 4
Remote input (RX) 32 points 128 points
Remote output (RY) 32 points 128 points
Remote register (RWw) 4 points 16 points
Remote register (RWr) 4 points 16 points