User's Manual
12 - 10
12. CC-Link IE FIELD NETWORK CONNECTION
12.4 PLC Side Setting
12.4 PLC Side Setting
This section describes the settings of the GOT and CC-
Link IE controller network module in the following case of 
system configuration.
POINTPOINTPOINT
CC-Link IE Field Network Module
For details of the CC-Link IE Field Network module,
refer to the following manual.
CC-Link IE Field Network Master/Local Module 
User's Manual
 System configuration
(Network Type: CC IE Field)
*1 The CC-Link IE Field Network module is mounted on slot 0 
of the base unit.
The start I/O No. of the CC-Link IE Field Network module is 
set at [0].
POINTPOINTPOINT
When connecting to Q170MCPU
When connected to Q170MCPU, the start I/O No. of
the CC-Link IE Field Network module is set to "70".
 Parameter settings (Connection to MELSEC-
Q, QS series) of System configuration 
(Network Type: CC IE Field)
(1) Network parameter] of GX Works2
Use GX Works2 of Version 1.31H or later.
(a) Network parameter
: Necessary  : As necessary  : Not necessary
*1 When using Q170MCPU, set it according to the system 
configuration.
*2 Specify the same network No. as that of the GOT.
*3 Set the same mode setting as that of the GOT.
<CC-Link IE Field Network module> *
1
(Use the default value for settings other than the following.)
 Station No.   : 0 (fixed)
 Mode     : Online (normal)
 Network type   : CC IE Field (Master station)
 Network No.   : 1
 Total stations   : 1
 Network Configuration Settings :
CC-Link IE Field Network
<GOT> 
(Use the default value for settings other 
 than the following.)
RX/RY00H to FFH
RW
W/RWr00H to FFH
Network type   : CC IE Field
Network No.   : 1
Station No.   : 1 
Mode Setting : Online 
Network Configuration Settings :
Monitor Speed : High
RX/RY00 to FFH
RWW/RWr00 to FFH 
■ GT Designer3 [Communication setting] of System 
configuration1 (Network Type: CC IE Field)
■ [Network parameter] of GX Works2
Item Set value
Setting 
necessity at 
GOT 
connection
Network type
CC IE Field
(Master station) (fixed)
Starting I/O No.
*1
0000H
Network No.
*2
1
Total stations 1
Station No. 0 (fixed)
Mode
*3
Online
(Normal mode)
Network Configuration 
Settings
Refer to (b)
Refresh parameters
(Use default value)
Interrupt settings
Interlink transmission 
parameters
Routing parameters Refer to (c)