User's Manual
10 - 24
10. MELSECNET/10 CONNECTION (PLC TO PLC NETWORK)
10.4 PLC Side Setting
(2) Network range assignment
: Necessary  : As necessary  : Not necessary
*1 Be sure to set it to perform the cyclic transmission.
POINTPOINTPOINT
When changing the network parameter
After writing the network parameter to the PLC CPU,
operate the PLC CPU ether turning OFF and then ON
or resetting.
(3) Routing parameter setting
Up to 64 [Transfer Network No.]s can be set.
However, the same transfer network number cannot be 
set twice or more (multiple times).
Therefore, the one that can access to other station from 
the request source host GOT is 64 kinds of [Transfer 
Network No.]s.
POINTPOINTPOINT
Routing parameter setting of request source
Routing parameter setting is also necessary for the
request source GOT.
For the setting, refer to the following.
10.3.3 Routing parameter setting
Item Set value
Setting 
necessity at 
GOT 
connection
Monitoring time 200
LB/LW 
setting
*1
Send 
range 
for 
each 
station 
(LB)
Station 
No.1
Start 0000
H
End 00FFH
Station 
No.2
Start 0100
H
End 01FFH
Send 
range 
for 
each 
station 
(LW)
Station 
No.1
Start 0000
H
End 00FFH
Station 
No.2
Start 0100
H
End 01FFH
LX/LY setting
*1
No setting
Specify I/O master station*1 No setting
Specify reserved station No setting
Supplementary setting
(Use default value)
Station inherent parameters
Item Range
Target network No. 1 to 239
Relay network No. 1 to 239
Relay station No. 1 to 64