9. MELSECNET/H CONNECTION (PLC TO PLC NETWORK)
9.3 GOT Side Settings
9 - 9
9
MELSECNET/H 
CONNECTION (PLC 
TO PLC NETWORK)
10
MELSECNET/10 
CONNECTION (PLC 
TO PLC NETWORK)
11
CC-Link IE CONTROLLER 
NETWORK 
CONNECTION
12
CC-Link IE FIELD 
NETWORK 
CONNECTION
13
CC-Link CONNECTION 
(INTELLIGENT DEVICE 
STATION)
14
CC-Link 
CONNECTION 
(Via G4)
15
INVERTER 
CONNECTION
16
SERVO AMPLIFIER 
CONNECTION
9.3 GOT Side Settings
9.3.1 Setting communication 
interface (Communication 
settings)
Set the channel of the connected equipment.
1. Select [Common]   [Controller Setting] from the 
menu.
2. The Controller Setting window is displayed. Select the 
channel to be used from the list menu.
3. Set the following items.
• Manufacturer: Mitsubishi
• Controller Type: Set according to the Controller 
Type to be connected.
• I/F: Interface to be used
• Driver: MELSECNET/H
4. The detailed setting is displayed after Manufacturer, 
Controller Type, I/F, and Driver are set.
Make the settings according to the usage 
environment.
 9.3.2 Communication detail settings
Click the [OK] button when settings are completed.
POINTPOINTPOINT
The settings of connecting equipment can be
confirmed in [I/F Communication Setting].
For details, refer to the following:
1.1.2 I/F communication setting
9.3.2 Communication detail settings
Make the settings according to the usage environment.
2.
3.
4.
Click!
Item Description Range
Network Type
Set the network type.
(Default: MNET/H mode)
• MNET/H mode
• MNET/10 mode
• MNET/H 
Extended 
mode
*1
Network No.
Set the network No.
(Default: 1)
1 to 239
Station No.
Set the station No. of the GOT.
(Default: 1)
1 to 64
Mode Setting
Set the operation mode of the 
GOT.
(Default: 
Online (auto. reconnection))
•Online
(auto. 
reconnection)
• Offline
• Test between
slave station
*2
• Self-loopback 
test
*2
• Internal self-
loopback
test
*2
• H/W test
*2
Retry
Set the number of retries to be 
performed when a communication 
timeout occurs.
When no response is received 
after retries, a communication 
times out.
(Default: 3times)
0 to 5times
Timeout
Time
Set the time period for a 
communication to time out.
(Default: 3sec)
3 to 90sec
Delay
Time
Set the delay time for reducing the 
load of the network/destination 
PLC.
(Default: 0ms)
0 to 300ms