User's Manual
8 - 50
8. ETHERNET CONNECTION
8.5 Precautions
 When setting IP address
Do not use "0" and "255" at the end of an IP address.
(Numbers of *.*.*.0 and *.*.*.255 are used by the 
system)
The GOT may not monitor the controller correctly with 
the above numbers.
Consult with the administrator of the network before 
setting an IP address to the GOT and controller.
 When monitoring to another network No. on 
the same line
When the network No. of the GOT does not match with 
that of the PLC on the same Ethernet, the PLC cannot 
be monitored. When monitoring, set the same network 
No. as that of the GOT, or connect a Ethernet module to 
the PLC and set the routing setting to monitor as other 
network.
When the Multi-channel is supported for GT16, set 
each channel with the networks No. to monitor.
 Remote password for QCPU
Do not set a remote password for QCPU.
Monitoring with GOT becomes unavailable.
 When connecting to Built-in Ethernet port of 
Built-in Ethernet port CPU
Connect to GOT after turning on the network equipment 
such as Built-in Ethernet port CPU or HUB to enable 
the communication.
When the communication with Built-in Ethernet port 
CPU is not available, a communication error may occur 
on the GOT.
 The number of connectable CPUs for one 
GOT
QCPU : 128 CPUs can be set (10 or less CPUs are 
recommended)
FXCPU : 128 CPUs can be set (10 or less CPUs are 
recommended)