4. HOW TO MONITOR REDUNTANT SYSTEM
4.10 Switch the Monitor Target to the Control System Using the Script Function
4 - 33
1
PREPARATORY 
PROCEDURES FOR 
MONITORING
2
DEVICE RANGE 
THAT CAN BE SET
3
ACCESS RANGE 
FOR MONITORING
4
HOW TO MONITOR 
REDUNTANT 
SYSTEM
5
BUS CONNECTION
6
DIRECT 
CONNECTION TO 
CPU
7
COMPUTER LINK 
CONNECTION
8
ETHERNET 
CONNECTION
3. Create a monitor screen.
For MELSECNET/H connection, MELSECNET/10 connection or Ethernet connection: (Common)
In the device setting (network setting) of each object, set Network No. 1 and Station No. 1 of the control system.
4. Validate the station number switching function.
On the Basic tab screen specified by selecting [Screen]   [Screen Property], select the item [Switch Station No.] to 
validate the station number changing function.
Make this setting for each monitor screen.
5. Change the station number switching device value in the script.
By selecting [Common]   [Script]   [Script], create a script for each monitor screen that checks the SM1515 
status of the current monitor station, and if it is OFF (standby system), changes the station number switching device 
value.
Set the trigger type of the script as [Ordinary] or [Sampling(about 3s)].
• Screen script for MELSECNET/H connection and MELSECNET/10 connection:
Set the created script for each screen on the Screen tab.
// If the host station is not a control station, the station number is switched to that of the other station.
if([b:SM1515]==OFF){
if([w:GD100]==1){
[w:GD100]=2;
}else{
[w:GD100]=1;
}
}
Check here.