. ELECTRICAL WORK............................................................................................................................................ H2iSD-2 1-1. General Cautions........................................................................................................................................ H2iSD-2 1-2. Power Supply for Indoor Unit and Outdoor Unit.......................................................................................... H2iSD-3 2. M-NET CONTROL..............
1. ELECTRICAL WORK 2010 H2i ® Y-SERIES SYSTEM DESIGN 1-1. General Cautions Follow ordinance of your governmental organization for technical standard related to electrical equipment, wiring regulations, and guidance of each electric power company. Wiring for control (hereinafter referred to as transmission cable) shall be (50mm[1-5/8in] or more) apart from power source wiring so that it is not influenced by electric noise from power source wiring.
1. ELECTRICAL WORK 1-2.
2010 H2i ® Y-SERIES SYSTEM DESIGN 1. ELECTRICAL WORK Model Hz PCFY-P15NKMU-E PCFY-P24NKMU-E PCFY-P30NKMU-E PCFY-P36NKMU-E 60Hz PKFY-P06NBMU-E PKFY-P08NBMU-E PKFY-P12NHMU-E PKFY-P15NHMU-E PKFY-P18NHMU-E PKFY-P24NKMU-E PKFY-P30NKMU-E 60Hz PFFY-P06NEMU-E PFFY-P08NEMU-E PFFY-P12NEMU-E PFFY-P15NEMU-E PFFY-P18NEMU-E PFFY-P24NEMU-E 60Hz PFFY-P06NRMU-E PFFY-P08NRMU-E PFFY-P12NRMU-E PFFY-P15NRMU-E PFFY-P18NRMU-E PFFY-P24NRMU-E 60Hz Symbols: MCA : Min.Circuit Amps (=1.
1. ELECTRICAL WORK 1-2-2. Electrical characteristics of Outdoor unit of cooling mode Model Unit Combination Hz Volts Voltage range Outdoor Units MOCP : Max. Over Current Protection RLA : Rated Load Amps RLA(A) RLA(MAX)(A) MCA(A) MOCP Compressor Fan SC(A) Output(kW) PUHY-HP72TJMU-A 60Hz 208 / 230V 19.4 / 17.6 38.4 / 38.4 59 / 54 101 / 92 15 0.92 PUHY-HP96TJMU-A 60Hz 208 / 230V 28.2 / 25.5 52.4 / 52.4 74 / 68 127 / 116 15 0.
2. M-NET CONTROL 2-1-1. Using MA Remote controller Long transmission cable causes voltage down, therefore, the length limitation should be obeyed to secure proper transmission. Max. length via Outdoor (M-NET cable) L1+L2+L3+L4, L1+L2+L6+L7, L3+L4+L6+L7 <=500m[1640ft.] 1.25mm2 [AWG16] or thicker Max. Total M-NET Wiring <=2km [6,560ft.] 1.25mm2 [AWG16] or thicker ∑ (L1 → 8) <=200m[656ft.] 1.25mm2 [AWG16] or thicker Max. length to Outdoor (M-NET cable) L1+L8, L3+L4, L6, L2+L6+L8, L7 Max.
2. M-NET CONTROL 2-2. Transmission Cable Specifications Type of cable ME Remote controller cables Cable size Remarks Connected with simple remote controller. 1.25 [AWG16] — MA Remote controller cables Sheathed 2-core cable (unshielded) CVV Shielding wire (2-core) CVVS, CPEVS or MVVS 1.25 1.25 2 2 [AWG16] [AWG16] When 10m [32ft] is exceeded, use cables with the same specification as transmission cables. 1.25 1.
2. M-NET CONTROL 2010 H2i ® Y-SERIES SYSTEM DESIGN 2-3. System Configuration Restrictions 2-3-1. Common restrictions for the CITY MULTI system For each Outdoor unit, the maximum connectable quantity of Indoor unit is specified at its Specifications table. A) 1 Group of Indoor units can have 1-16 Indoor units; B) Maximum 2 remote controllers for 1 Group; (MA/ME remote controllers cannot be present together in 1group.
2. M-NET CONTROL 2-3-3. Ensuring proper power supply to System controller 2-3-3-A. When connecting to TB3 of the Outdoor unit and receiving power from the Outdoor unit. Maximum 3 System controllers can be connected to TB3. If there is more than 1 Outdoor unit, it is necessary to replace power supply switch connector CN41 with CN40 on one Outdoor unit. Fig.
2. M-NET CONTROL 2010 H2i ® Y-SERIES SYSTEM DESIGN 2-3-4. Power supply to LM adapter LMAP03U 1-phase 208-230V AC power supply is needed. The power supply unit PAC-SC51KUA is not necessary when connecting only the LMAP03U. Yet, make sure to change the power supply changeover connector CN41 to CN40 on the LM adapter. 2-3-5. Power supply to BM ADAPTER 1-phase 100-240VAC power supply is needed. The power supply unit PAC-SC51KUA is not necessary when only BM ADAPTER is connected.
2. M-NET CONTROL 2-4. Address Setting 9 01 7 8 7 8 01 2 3 9 2 3 D BC E Unit address No. setting 45 6 F 0 12 3456 789A À Address No. of outdoor unit, indoor unit and remote controller. The address No. is set at the address setting board. In the case of R2 system, it is necessary to set the same No. at the branch No. switch of indoor unit as that of the BC controller connected. (When connecting two or more branches, use the lowest branch No.
2. M-NET CONTROL 2-4-2. Rule of setting address 7 8 7 8 45 6 01 7 8 9 01 45 6 45 6 45 6 10 1 0 0 0 100 10 1 0 0 10 1 0 0 0 100 10 1 9 0 1 9 0 1 7 8 0 100 7 8 Lowest address within the indoor units connected to the BC controller (Sub) plus 50. The smallest address of indoor unit in the group + 100 The place of "100" is fixed to "1" The address of main remote controller + 50 The address automatically becomes "200" if it is set as "00" The smallest group No.
2. M-NET CONTROL 2-4-3. System examples 2010 H2i ® Y-SERIES SYSTEM DESIGN Factory setting Original switch setting of the outdoors, indoors, controllers and LMAP at shipment is as follows.
2. M-NET CONTROL 2010 H2i ® Y-SERIES SYSTEM DESIGN 2-4-3-2.
2. M-NET CONTROL 2-4-3-3.
2. M-NET CONTROL 2010 H2i ® Y-SERIES SYSTEM DESIGN 2-4-3-4. ME remote controller, Single-refrigerant-system, No system controller PUHY-HP-TSJMU OC OS 51 CN40 CN41 52 CN40 DipSW2-1 OFF TB3 *1 PUHY-HP-TJMU OC 51 CN41 CN40 DipSW2-1 CN41 DipSW2-1 OFF OFF TB3 *2 TB3 Group 1 To *1 or *2 Group 2 Group 3 Group 4 Indoor unit 01 02 TB5 03 TB5 04 TB5 05 TB5 TB5 101 102 104 ME R/C ME R/C ME R/C 105 155 ME R/C ME R/C NOTE: 1.
2. M-NET CONTROL 2-4-3-6.
2. M-NET CONTROL 2010 H2i ® Y-SERIES SYSTEM DESIGN 2-4-3-7.
2.
2-4-3-10. LMAP LMAP can transmit max. 50 indoor units; If system controller (SC) is used, DipSW1-2 at LMAP and DipSW2-1 at Outdoor unit should set to "ON". Change Jumper from CN41 to CN40 to activate power supply to LMAP itself for those LMAP connected without system controller (SC). LMAP(01) LMAP can transmit for max. 50 indoor units in single-refrigerant-system or multi-refrigerant-system.
2. M-NET CONTROL BM ADAPTER(01) HUB 000 CN40 CN41 BM ADAPTER can transmit for max. 50 indoor units in single-refrigerant-system or multi-refrigerant-system.
3. PIPING DESIGN Refrigerant pipe for CITY MULTI shall be made of phosphorus deoxidized copper, and has two types. A. Type-O : Soft copper pipe (annealed copper pipe), can be easily bent with human's hand. B. Type-1/2H pipe : Hard copper pipe (Straight pipe), being stronger than Type-O pipe of the same radical thickness. The maximum operation pressure of R410A air conditioner is 4.30 MPa [623psi] . The refrigerant piping should ensure the safety under the maximum operation pressure.
3. PIPING DESIGN 3-2. Piping Design OU Note1. No Joint after Header; Piping direct to Indoor Unit from Header; Note2. If the A/C system is designed to use Cooling-mode under Outside temperature 10°C [50°F], H'<=40m [131ft.]; Note3. As bents cause pressure loss on transportation of refrigerant, fewer bents design is better; Piping length needs to consider the actual length and equivalent length which bents are counted. Equivalent piping length = Actual piping length + "M" x Quantity of bent.
3. PIPING DESIGN Note1. No Joint after Header; Piping direct to Indoor Unit from Header; Note2. If the A/C system is designed to use cooling-mode under outside temperature 10°C [50°F], H’<=40m [131ft]. Note3. As bents cause pressure loss on transportation of refrigerant, fewer bents design is better; Piping length needs to consider the actual length and equivalent length which bents are counted. Equivalent piping length=Actual piping length+"M" x Quantity of bent.
3. PIPING DESIGN 3-3. Refrigerant Charge Calculation (1) Calculation of additional refrigerant charge Calculate the amount of additional charge based on the length of the piping extension and the size of the refrigerant line. Use the table to the below as a guide to calculating the amount of additional charging and charge the system accordingly. If the calculation results in a fraction of less than 0.1kg, round up to the next 0.1kg. For example, if the result of the calculation was 12.
4. OUTDOOR INSTALLATION 2010 H2i ® Y-SERIES SYSTEM DESIGN 4-1. Installation Site Requirements 1. 2. 3. 4. 5. 6. 7. Do not install in an area where the unit could be subjected to direct heat. Avoid installing the unit in a location where the operating sound could be an annoyance. Avoid the sites where strong winds blow. Install on a stable, load-bearing surface. Ensure there is adequate drain flow from the unit when in heating mode See space requirements for installation and maintenance.
4. OUTDOOR INSTALLATION 4-2. Installation Clearance Space • Secure enough space around the unit as shown in the figure. : Top view A : Front C : Back : Side view B : Unit height D : Air outlet guide (Procured at the site) 2010 H2i ® Y-SERIES SYSTEM DESIGN In case of single installation : When there is little space up to an obstruction (1) If the distance is 300 mm [11-13/16 in.
4.
4. OUTDOOR INSTALLATION 4-3. Piping Direction · When lifting the unit with ropes, run the ropes under the unit and use the lifting hole. · Support the unit at four points with two ropes, and avoid giving mechanical shock. · Suspension rope angle must be 40° or less, so as to avoid compressing fan guard. · Use two ropes, each at least 8m [26 ft.] in length · Use ropes strong enough to support the weight of the unit. · Always suspend the unit from four corners.
4. OUTDOOR INSTALLATION · Secure the unit with anchor bolts as shown in the figure below so that the unit will not topple over with strong wind or during an earthquake. · Install the unit on a durable base made of such materials as concrete or angle steel. · Ta ke appropriate anti-vibration measures (e.g., vibration damper pad, vibration isolation base) to keep vibrations and noise from being transmitted from the unit through walls and floors.
4. OUTDOOR INSTALLATION 4-3-4.
4. OUTDOOR INSTALLATION The tilt angle of the twinning pipe The tilt angle of the twinning pipe must be within ±15° with the horizontal plane. Tilting the twinning pipe more than specified will cause damage to the unit. The length of the straight part of the pipe before the branching For the twinning kit, always use the accessory piping parts. The length of the straight part of pipe connected in front of the twinning pipe must be 500 mm (19 in) or longer.
4. OUTDOOR INSTALLATION 4-3-7. Twinning on the outdoor unit side 2010 H2i ® Y-SERIES SYSTEM DESIGN See the following drawing for connecting the pipes between the outdoor units. Field piping Twinning kit Field piping The le mus ngth of t be t 500 he straig mm [19 i ht pipe n.] o r lon ger Field piping Twinning kit Field piping The le mus ngth of t be t 500 he straig mm h [19 i t pipe n.
4. OUTDOOR INSTALLATION • Snow hood 906 [35-11/16] Unit : mm[in] 800 [31-1/2] 750 [29-17/32] 1324 [52-5/32] (920 [36-1/4]) 86 [3-13/32] (760) [29-15/16] H 2010 H2i ® Y-SERIES SYSTEM DESIGN 4-4. Weather Countermeasures (See Note 1) 453 [17-27/32] 910 [35-27/32] 453 [17-27/32] 760 [29-15/16] 453 [17-27/32] Outlet Inlet Note: 1.Height of frame base for snow damage prevention (H) 12 inches above the average snowfall.
4. OUTDOOR INSTALLATION 4-5. Low Ambient Kit Application Guidelines General Unit Placement and Clearances Top View 2010 H2i ® Y-SERIES SYSTEM DESIGN • Outdoor units should be located in an area protected from prevailing winds. • In high wind locations, it may be advisable to install the outdoor units within a walled area. • Hood discharge should be directed away from or perpendicular to the prevailing winds. Do not direct the hood discharge towards prevailing winds.
4. OUTDOOR INSTALLATION 2010 H2i ® Y-SERIES SYSTEM DESIGN Additional Rooftop Mounting Guidelines Ground-level installation is preferred for outdoor units that include a low ambient kit. If ground-level installation is not possible, follow general, as well all additional installation guidelines for rooftop mounting. If you have any questions, please contact your distributor. Note: Low ambient hood(s) increase the overall height of the outdoor units and make them more susceptible to wind stresses.
5. STANDARD AND SEACOAST (BS) PROTECTION TREATMENT 5-1.
6. CAUTIONS 2010 H2i ® Y-SERIES SYSTEM DESIGN The installer and/or air-conditioning system specialist shall follow local safety regulations and standards regarding refrigerant leakage. The following standard may be applicable if a local regulation or standard is available. 6-1. Refrigerant Properties R410A refrigerant is harmless and incombustible. R410A is heavier than the indoor air in density. Leakage of the refrigerant in a room has possibility to lead to a hypoxia situation.