PLC Ladder Monitor Operation Manual 4-3
Timer/Counter Value Change Screen Restrictions
You cannot change the setup value when the indexed device, the link direct device
(J\) or the intelligent function unit (U\G) is specified.
To display the ladder program after changing the value, you need to read and display the
ladder again.
When using Universal Model QCPU, you need to set the time of [timeout] longer than the
[Transfer time of program memory batch-transfer].
The communication error will occur, if the time of [timeout] set shorter than [Transfer
time of program memory batch-transfer].
See the following pages for the setting of [timeout].
Reference:GP-Pro EX Device Connection Manual
See the following manuals for the contents of [Transfer time of program memory
batch-transfer].
Reference:External Device manual
You can change the value of a program located at the first number of the settings screen
that appears after executing “PC Parameter Scan Execution Program”. Even if multiple
programs exist in CPU, the timer/counter values of all the programs is not changed.
Ladder program password settings are not supported. When a [Stop Read/Write]
password is used, changing a setup value will cause a communication error.